Figure; Enable/Disable Zone 3 Remote Temperature Sensor; Manual 2100-676B - Bard MULTI-TEC W24AAPA Installation Instructions Manual

Wr series wall-mount air conditioner lc6000-100 controller free cooling unit system
Table of Contents

Advertisement

FIGURE 50

Enable/Disable Zone 3 Remote Temperature Sensor

6. Enter Total Number of Units
1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to Sys Config;
press ENTER key.
4) Press UP or DOWN keys to scroll to General;
press enter key.
5) Press ENTER key to scroll to Total Units (see
Figure 51).
6) Press UP or DOWN keys to adjust value to
correct number of units.
7) Press ENTER key to save value.
8) Press the ESCAPE key several times to return
to Main Menu screen.
FIGURE 51
Total Units Displayed
7. Verify Units Are Online
Once a unit is uniquely addressed, communication
can be verified at the LC controller.
With the correct number of units set at the LC
controller, each unit can be remotely viewed from
the controller information screen.
To view these screens:
1) Press ESCAPE key to view the Status screen.
(May need to be pressed more than once.)

Manual 2100-676B

Page
86 of 88
2) Press UP or DOWN key until the Quick Menu in
the lower right corner of the screen displays the
Information icon (
3) Press UP or DOWN keys to scroll through the
Information screens until the desired unit
Information screen appears.
In addition to being able to remotely view the units,
an alarm will be generated on the LC controller for
units not communicating.
8. Clear Controller Alarm Logs
To clear the LC controller alarm logs:
1) Press MENU key to go to the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to enter
USER password 2000.
3) Press UP or DOWN keys to scroll to Settings;
press ENTER key.
4) Press UP or DOWN keys to scroll to
Initialization; press ENTER key.
5) Press ENTER key to scroll to Delete Alarm
Logs? (see Figure 52).
6) Press UP or DOWN key to value to YES; press
ENTER key.
7) Press ESCAPE key several times to return to
Main Menu screen.
FIGURE 52
Clearing LC6000 Alarm Logs
9. Complete Installation
Once all the installation steps have been
completed, all alarms and alarm logs have been
cleared and system verification and run test results
were satisfactory, the installation can now be
considered "complete".
Additional programming information can be found
in WR Series Service Instructions 2100-665 and
LC6000 Service Instructions 2100-669.