Unit Control Voltage Wiring; Manual 2100-676B - Bard MULTI-TEC W24AAPA Installation Instructions Manual

Wr series wall-mount air conditioner lc6000-100 controller free cooling unit system
Table of Contents

Advertisement

Unit Control Voltage Wiring

230/208V 1 phase and 3 phase equipment use dual
primary voltage transformers. All equipment leaves the
factory wired on 240V tap. It is very important that
the correct voltage tap is used. For 208V operation,
reconnect from 240V to 208V tap. The acceptable
operating voltage range for the 240 and 208V taps are:
240V tap (253 – 216) and 208 tap (220 – 197). To
verify voltage and adjust voltage tap (if necessary), see
Figure 17.
NOTE: The voltage should be measured at the field
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition.

Manual 2100-676B

Page
64 of 88
FIGURE 16
Rear Communication and Power Wire Entrances (Optional)
OPTIONAL REAR
POWER WIRE ENTRANCE
OPTIONAL REAR
LOW VOLTAGE/COMMUNICATION
ENTRANCE
LOW VOLTAGE/COMMUNICATION
ENTRANCE
UNIT POWER ENTRANCE
LIQUID TIGHT CONDUIT MUST
NOT PASS THIS LINE TO
PREVENT DAMPER BLADE
INTERFERANCE
LIQUID TIGHT CONDUIT
SECURE TO KEEP CLEAR
OF HEATER ELEMENT
CONDUIT ROUTE THROUGH
RUBBER BUSHING
MIS-3926

Advertisement

Table of Contents
loading

Table of Contents