Supply Air Temperature; Duct Air Temperature Sensor; Relative Humidity Sensor; Indoor Air Quality (Co2) Sensor - Carrier 3V VVT 33ZCVVTZC-01 Installation And Start-Up Instructions Manual

Pressure dependent control zone controller
Hide thumbs Also See for 3V VVT 33ZCVVTZC-01:
Table of Contents

Advertisement

MECHANICAL
CLAMP
STOP
ASSEMBLY
Assembled
in USA
wal(
by Belimo
for
CARRIER
@
Override
35 in-lb (4 Nm)
80..110s
24VAC/DC
50/60Hz
3VA
2W
/
WIRING
KNOCKOUTS
/
ACTUATOR
MANUAL
OVERRIDE
SWITCH
/
MOTHERB©ARD
ACCESS
Fig. 2 -- Zone
Controller
WIRING
ACCESS
SUPPLY
AIR TEMPERATURE
(SAT)
SENSOR
-- The
33ZCSENSAT
supply
air temperature
sensor
is required
for
reheat applications
or stand-alone
operation. The sensor has an
operating range of -40 to 245 F (-40 to 118 C) and includes a
6-in. sttfinless steel probe and cable.
DUCT AIR TEMPERATURE
SENSOR -- The 33ZCSENDAT
Duct Air Temperature
Sensor is required for cooling only appli-
cations on non-33CS or non-Career
dmnpet_. The sensor is used
for supply tilt monitoring.
The sensor has an operating range of
_40 to 245 F (-40 to 118 C) and includes a mounting grommet
and 75-in. cable.
RELATIVE
HUMIDITY
SENSOR
--The
33AMSENRHS000
relative
humidity
sensor
is required
for zone
humidity
control
(dehumidification)
when
in a linked
system
with
a rooftop
unit
equipped
with
a dehumidification
device.
Othet-wise,
the RH
sensor
is used for monitoring
only.
NOTE:
The relative
humidity
sensor
and CO 2 sensor
cannot
be
used on the same zone
controllet:
INDOOR
AIR
QUALITY
(CO2)
SENSOR
--
An indoor
fur
quality
sensor
is
required
for
optional
demand
control
ventilation.
The 33ZCSENCO2
CO 2 sensor
is an indoor,
wall
mounted
sensor
with
an LED
display.
The 33ZCT55CO2
and
33ZCT56CO2
CO 2 sensors
tue indoor,
wall-mounted
sensors
without
display.
NOTE:
The relative
humidity
sensor
and CO 2 sensor
cannot
be
used on the same zone
controllet:
Mount
Zone
Controller
(Retrofit
Applica-
tions)
--
The zone controller
is factory-tnounted
on Cturier
round
and rectangular
dampers.
When
retrofitting
a zone
controller
on an existing
dmnper,
perform
the following
procedures.
LOCATION
-- The zone controller
must be mounted on the
air temfinal's
damper actuator shaft. For service access, there
should be at least 12 in. of clearance
between the front of the
zone controller and adjacent surfaces. Refer to Fig. 3.
MOUNTING-
Perform
the following
steps to mount
the
zone control let:
1. When
retrofitting
a zone
controller
on an
existing
damper, prior to inst_dling the zone controllet: remove all
existing hardware.
2. Round or rectangular
&_mper brackets may be attached to
the dmnper to provide a cle_uance for the &Lmper be_uing
when the zone controller is inst_dled on older style VVT®
dmnpers.
The zone controller
is used to determine
the
location of the bracket. Attach the bracket to the zone con-
troller using a single screw through the anti-rotation
tab.
3. Visually inspect the &_mper and determine
the direction
in which the &tmper shaft moves to open the &_mper-
clockwise
(CW) or counterclockwise
(CCW).
Refer to
Fig. 4.
If the &_mper rotates CCW to open, it does not require
any configuration
changes.
If the dmnper
rotates
CW to open,
then the &_mper
actuator
logic must
be reversed.
This
is done
in the
software
when performing
system st_ut-up and damper
calibration
test. Do not attempt to change &tmper rotation
by changing
wiring. This will upset the dmnper
position
feedback potentiometer
readings.
4. Rotate the damper shaft to the fully closed position. Note
direction of rotation.
5. Press the release
button on the actuator
and rotate the
clamp in the same direction that was required to close the
damper in Step 4.
6. Press the release
button on the actuator
and rotate the
actuator back one position graduation.
Release the button
and lock the actuator in this position.