Alarm Configuration Table; Terminal Service Configuration - Carrier 3V VVT 33ZCVVTZC-01 Installation And Start-Up Instructions Manual

Pressure dependent control zone controller
Hide thumbs Also See for 3V VVT 33ZCVVTZC-01:
Table of Contents

Advertisement

Table 5 -- Alarm Configuration Table
DESCRIPTION
Alarm Configuration
Re-alarm Time
Alarm Routing
SPT Occupied Hysteresis
Unoccupied
SPT
Low Limit
High Limit
Demand Ctrl Ventilation
Low Limit
High Limit
VALUE
UNITS
NAME
0
min
RETIME
00000000
ROUTING
5.0
"F
SPTHYS
40.0
dF
LOWLIM
99.0
dF
HIGHLIM
250.0
LOWLIM
1200.0
HIGHLIM
UNOCCUPIED
SPACE
IEMPERATURE
LOW
LIMIT
-- This configuration
defines the lowest temperature
that the
unoccupied
space can be before an tdarm is generated,
Unoccupied
Space
Temperature
L_w Limit:
Units
F (C)
Range
0 to 255 F
Default Value
40
UNOCCUPIED
SPACE
TEMPERATURE
HIGH
LIMIT
-- This configuration
defines the highest temperature
that the
unoccupied
space can be before an tdarm is generated,
Unoccupied
Space
Temperature
High Limit:
Units
F (C)
Range
0 to 255 F
Default Value
99
DEMAND
CONTROL
VENTILATION
LOW LIMIT -- This
configuration
defines
the lowest
CO 2 level reading that the
occupied space can have before an tflarm is generated,
Demand Control Ventilation
L_w Limit:
Units
ppm
Range
0 to 5000
Default Value
250
DEMAND
CONTROL
VENTILATION
HIGH LIMIT --This
configuration
defines
the highest
CO s level reading
that the
occupied space can have before an tflarm is generated,
Demand Control Ventilation
High Limit:
Units
ppm
Range
0 to 5000
Default Value
1200
Terminal
Service
Configuration
Table -- The Ter-
minal
Service
Configuration
Table
(CONFIG)
contains
decisions
used
to configure
the
main
settings
for the
zone
controller.
This
includes
Terminal
Type,
Primary
Inlet
Size,
and
gains
for the
damper
and
heating
PID
loops.
Decisions
regarding
auxiliary
heat
am
made
in this
table
and
up to
10 temperature
readings
can be configured
for l_)om tempera-
ture sensor
averaging.
SPT and SAT sensor
trimming
am done
hem as well. See Table 6.
TERMINAL
TYPE
--
This
configuration
is used
to indicate
the terminal
type that the zone
controller
is installed
on. A 1 is
for Single
Duct
termimfls,
a 2 is for Partdlel
Fan terminals,
and
a 3 is for Series
Fan terminals.
Terminal
Type:
Range
1 to 3
Default
Value
1
PRIMARY
INLET
SIZE
-- The Primtu'y
Inlet
Size configu-
ration
is used to input the inlet diameter
of the terminal
if used
with a round
inlet. The Inlet Area
configuration
is used for oval
or lectangular
inlets.
The zone controller
will use the larger
val-
ue for cfin calculations
if both
values
are configured.
NOTE:
Carrier
sizes
12, 14, and
16 are oval.
Primary
Inlet Size
(Inlet Diameter):
Units
Inches
Range
0.0 to 24.0
Default
Value
6.0
INLET
AREA
--
The Inlet Area configuration
is used if the ter-
minal
has tm ovid or mctanguku"
inlet. The
Primtuy
Inlet Size
configuration
is used for l_)und inlets. The zone controller
will use
the kuger vtflue for cfin calculations
if both values am configured.
Inlet Area:
Units
Squtu'e
Inches
Range
0.0 to 500.0
Default
Value
0.0
DAMPER
LOOP
PARAMETERS
-- The
loop
gains
and
start value
define
how the temiinal
will respond
to deviations
in
measured
temperature
in order contl_)l to the damper
position.
The Proportional
Gain
is calculated
each time the ailt]ow
is
compared
to the active
airflow
set point.
As the enor
fi__)m set
point
goes to zero, file proportional
temi
will also go to zero.
The
Integral
Gain
is a running
summation
of all integral
terms
since the loop sttu-ted. This has file effect
of trimming
off
any offset
from
file set point
which
might
occur,
if only
the
proportional
term
existed.
Normally
a propollional
loop
with
no integral
term
would
require
frequent
adjustments
of the
starting
value to eliminate
the offset as static pressure
and other
conditions
change.
The derivative
gain tends to nullify
or accelerate
the chang-
es in the pl_)pollional
gain
depending
on the
size of the enor
from
the
set point.
This
allows
the damper
to respond
faster
and morn
efficiently
to accurately
maintain
the space
tempera-
ture set points.
The Start
Value
is the initial
value
that is then
modified
by the error
terms
of the PID c_dculation.
Damper
Loop
Partuneters
Proportional
Gain: Range
00.0 to 99.9
Default
Value
10.0
Integral Gain:
Range
00,0 to 99,0
Default Value
2,5
Derivative Gain:
Range
00.0
Default Value
4,0
Start Value:
Units
%
Range
0 to 100
Default
Value
40
CLOCKWISE
ROTATION
--
This
configuration
is used
to
define
what effect
a clockwise
rotation
of the actuator
will have
on the &Lmpel: If the actuator
rotates
clockwise
to closed
posi-
tion, the configuration
should
be set to Close.
If the actuator
ro-
tates
clockwise
to open,
file configuration
should
be
set to
open.
This
configuration
is used
to change
the rotation
of the
actuator
so that
the
&tmper
transducer
calibmfion
will
work
properly.
The actuator
does not have to be m-insttflled
nor tiny
switches
changed
to reverse
the action.
Clockwise
Rotation:
Range
Close/Open
Default
Value
Close
3O