Status Table - Carrier 3V VVT 33ZCVVTZC-01 Installation And Start-Up Instructions Manual

Pressure dependent control zone controller
Hide thumbs Also See for 3V VVT 33ZCVVTZC-01:
Table of Contents

Advertisement

6. The zone controller will send a llsystem z one d mnpers to
theirconfgured m inimum positions anddisplay the
v_dues. Check t hesystem bypass p ressure andsetthe
pressure set p oint. A djust minimum damper set p oints i f
required.
7. If fileuser f orces a nyzones t oa newposition, thenew
position i swritten tothezone's m inimum dmnper posi-
tionconfiguration
value a nd the dmnper isrepositionedi
8. Enable the Position Single Z one point.
9. The zone controller will send a llsystem z one d mnpers to
theirconfigured maximum positions anddisplay the
v_dues.
10. If the user forces any zones toanew position, the new po-
sition iswritten tofilezone's maximum d amper position
configuration
value a nd filedalnper isrepositionedi
11.At thistime, t heuser c an force the Bypass Pressure set
point. T ypic_flly, themaximum u nitrated ductstatic is
used. T hezone controller will thenwritetheforced
Bypass Pressure setpointtothesetpointtable in the
Bypass Controller bycommunicating
over t henetwork.
Thebypass controller will thenbegin tocontrol tothe
new bypass pressure
set p oint.
Status Table
--
The following
sections describe the com-
puter status screen which is used to determine
status the zone
controllec
The screens
shown may be displayed
differently
when using different Carrier soflwme. See Table 4.
TERMINAL
MODE
-- The terminal mode is determined
by
the equipment
mode as reported by linkage and space require-
ments determined
by space temperature
and set points. The
ZONE_BAL
and COMMISS
modes
am the result of the
activating
the commissioning
maintenance
table to perform
terminal testing and commissioning.
Terminal Mode:Display
Units
ASCII
Default Value
COOL
Display Range
HEAT.
COOL,
VENT,
REHEAT,
PRESSURE,
EVAC, OFF, ZONE_BAL,
COMMISS
Network Access
Read only
TERMINAL
TYPE--Terminal
type is the confirmation
of
the terminal type configuration
in the CONFIG Service Config
table.
Terminal Type:
Display Units
ASCII
Default value
SINGLDUCT
Display Range
SINGLDUCT.
PAR
FAN, SER FAN
Network Access
Read only
CONTROLLING
SETPOINT
-- Controlling
Set Point will
display either the heating master reference or the cooling mas-
ter reference depending
upon what mode the terminal is in. The
display will default to the heating master reference and display
the last controlling
master reference
when in neifller heating
nor cooling.
Controlling
Setpoint:
Display Units
F (C)
Default Value
-40
Display Range
-40 to 245
Network Access
Read only
SPACE TEMPERATURE
--Space
temperature
from 10 k_)
thermistor
(Type II) located in the space.
Space
Temperature:
Display Units
F (C)
Default Value
-40.0
Display Range
-40.0 to 245.0
Network Access
Read/Write
DAMPER POSITION-
Damper position percent range of
rotation determined by the transducer calibration procedure.
The zone controller is designed be used on dalnpers with any
range of rotation.
Damper
Position:
Display Units
% open
Default Value
0
Display Range
0 to 100
Network Access
Read only
SUPPLY AIR TEMPERATURE -- Temperature of the air
leaving the zone controller downstremn of any ducted heat
source. Measured by a 10 k_2 thermistor (Type II). This tem-
perature is used to control the maximum dischmge air to the
space when local heat is active. The sensor is not required or
recommended for cooling only terminals. If supply air temper-
ature display is required by specification, on a cooling only
box, a heat type other than zero must be configured. This
will have no adverse affect on the operation of a cooling only
terminal.
Supply
Air Temperature: Display Units
F (C)
Default Value
0.0
Display Range
-40.0 to 245.0
Network Access
Read/Write
LOCAL HEATING CAPACITY -- When loc_d heat at the
terminal is enabled the percent of heat being delivered is deter-
mined by the following formula for modulating (floating point)
type heat:
% Capacity = [(SAT - SPT)/(Maximum Duct Temp - SPT)]
The percent of heat delivered is determined by the follow-
ing for two-position hot water or staged electric heat:
% Output Capacity = (no. of active stages/Totedstages) * 100
Local Heating
Capacity:
Display Units
% output capacity
Default Value
0
Display range
0 to 100
Network Access
Read only
TERMINAL FAN -- The commanded output for the termimd
fan on a fan powered terminal.
Terminal Fan:
Display Units
Discrete ASCII
Default Value
Off
Display Range
Off/On
Network Access
Read/Write
RELATIVE HUMIDITY-
Space Relative Humidity read-
ing from the optional relative humidity sensor The humidity
reading is used for display and monitoring purposes only.
Relative
Humidity:
Display Units
% RH
Default Value
0
Display Range
0 to 100
Network Access
Read/Write
DEMAND VENTILATION--This
variable displays
the
amount of CO 2 in the air as read fiom the demand ventilation
sensor if DCV (demand control ventilation) is specified.
NOTE: The zone controller either reads relative humidity or
demand ventilation depending on what is specified in the Con-
trol Options configuration. If this point is not specifed, it is
awtilable for use as a soflwme point.
Demand
Ventilation:
Display Units
ppm
Default Value
0
Display Range
0 to 5000
Network Access
Read/Write
28