Table 10 -- Master Service Configuration Table
DESCRIPTION
VALUE
UNITS
NAME
Cool Start Avg. Demand
0.7
^F
CSA_DMD
Cool Mode Hysteresis
0.7
^F
C_HYST
Heat Start Avg. Demand
0.7
^F
HSA_DMD
Heat Mode Hysteresis
0.7
^F
H_HYST
System
Mode Reselect
30
min
RESELECT
Cool Time Guard Timer
0
min
C_MOD_TG
Heat Time Guard Timer
0
min
H-MOD_TG
Cont. Fan When Occ?
Yes
FAN_MODE
Heat Mode Lockout
Setp
140.0
dF
HLO_SPT
Cool Mode Lockout
Setp
-40.0
dF
CLO_SPT
COOL MODE
HYSTERESIS-
This
decision
is used to
configure the hysteresis
that will be used to determine when the
cooling
mode
will end. The cooling
mode ends when
the
avelage
cooling
demand
drops below the minimum
average
demand minus the hysteresis:
(average cooling demand < Cool
Start Avg. Demand -- Cool Mode Hysteresis)
Cool Mode
Hysteresis:
Units
delta F (C)
Range
0.5 to 5.0
Default Value
0.7
HEAT START AVERAGE
DEMAND
-- This
decision
is
used to configure
the minimum
average heating
demand
that
must be met before the system will st_ut in heating mode if no
mode is currently active.
NOTE:
If there is also an average
cooling demand,
and it is
also greater
than its configured
minimum
average
cooling
demand
(Cool Stml Avg. Demand),
then the mode with the
greater demand
will be selected.
If both heating
and cooling
average demand are exactly the same then the mode with the
greatest
individual
zone demand
will determine
the st_uting
system mode.
Heat St_u-t
Average Demand:
Units
delta F ((2_)
Range
0.5 to 5.0
Default Value
0.7
HEATMODE
HYSTERESIS--
This
decision
is used to
configure the hysteresis
that will be used to determine when the
heating mode will end. The heating mode ends when the aver-
age heating demand gets below the minimum
average demand
minus the hysteresis:
(average
heating
demand
< Heat SUut
Avg. Demand - Heat Mode Hysteresis)
Heat Mode
Hysteresis:
Units
delta F ((2_)
Range
0.5 to 5.0
Default Value
0.7
SYSTEM
MODE RESELECT--
This decision
is used to
configure
the minimum
time that must elapse before a mode
change can take effect.
System Mode
Reselect:
Units
minutes
Range
0 to 255
Default Value
30
COOL TIME
GUARD
TIMER -- This decision
is used to
configure the minimum
time that the cooling mode must be ac-
tive before
a mode change can take effect. The Cool Time
Guard Timer becomes active whenever
the cooling mode goes
into effect.
Cool Time
Guard Timer:
Units
minutes
Range
0 to 255
Default Value
0
HEAT
TIME
GUARD
TIMER
--
This
decision
is used
to
configure
the
minimum
time
that
the heating
mode
must
be
active
before
a mode
change
can take
effect.
The Heat
Time
Guard
Timer
becomes
active
whenever
the heating
mode
goes
into effect.
Heat Time
Guard Timer:
Units
minutes
Range
0 to 255
Default Value
0
CONT. FAN WHEN OCC -- This decision is used to config-
ure the air source fan to go On whenever the zone is in an occu-
pied mode. If this decision is set to No, the fan will cycle on
and off during occupied modes in order to maintain set point.
Cont. Fan
When Occ:
Range
No/Yes
Default Value
Yes
HEAT MODE LOCKOUT SET POINT -- This decision is
used to lock out the heating mode by comparing this value to
outdoor air temperature. If the outdoor air temperature reading
is v_flidand greater than this value then the heating mode will
be locked out. If outdoor air temperature drops 3 degrees below
the Heat Mode Lockout Set Point, the lockout is cancelled.
This 3-degree hysteresis
is fixed.
Heat Mode Lockout
Set Point:
Units
Range
Default Value
F (C)
-40.0 to 140.0
(140 = disable)
140
COOL MODE
LOCKOUT
SET POINT
-- This decision
is
used to lock out the cooling mode by comparing
this v_flue to
outdoor air temperature.
If the outdoor air temperature
reading
is v_flid and less than this value then the cooling mode will be
locked out. If outdoor air temperature
raises 3 degrees above
the Cool Mode Lockout
Set Point, the lockout is cancelled.
This 3-degree hysteresis
is fixed.
Cool Mode Lockout
Set Point:
Units
F (C)
Range
-40.0 to 140.0
(-40 = disable)
Default Value
M-0
Time Schedule
Configuration
Table
--
The Time
Schedule
Configuration
Table
(OCCDEFCS)
contains
decisions
used to configure
the zone controller's
occupancy
schedule. For flexibility of scheduling,
the occupancy
configu-
ration is broken into eight separate periods. See Table 11.
MANUAL
OVERRIDE
HOURS
-- The
Manu_fl
Override
Hours decision is used to command
a timed override by enter-
ing the number of hours the override will be in effect.
If the occupancy
schedule is occupied when this number
is
downloaded,
the current occupancy
period will be extended by
the number of hours downloaded.
36