Modulating Baseboard Hydronic Heating; Connect The Carrier Communicating; Communication Bus; Connection To The Communication - Carrier 3V VVT 33ZCVVTZC-01 Installation And Start-Up Instructions Manual

Pressure dependent control zone controller
Hide thumbs Also See for 3V VVT 33ZCVVTZC-01:
Table of Contents

Advertisement

O
//
1
Fig. 27 -- Wall Mounted Relative Humidity Sensor
Modulating
Baseboard
Hydronic
Heating -- In-
stall file water valve on the leaving water end of the baseboard
heatel_ See Fig. 30. Observe
the fluid flow direction
when
mounting the valve. Be sure to properly heat sink the valve and
direct the flmne away from the actuator and valve body when
sweating
file valve connections.
Install the leaving water tem-
perature sensor (33ZCSENCHG)
on the hydi_onic heating coil
as shown.
The sensor
accommodates
nominal
copper
pipe
fi_om I/2 to l-in. (OD sizes fi_m 5/8 to 1.125 in.). It should be
secured to the pipe with the clamp supplied. If piping is hu_ger
than l-in. nomimfl size, a field-supplied
clmnp must be used.
Use fiberglass pipe insulation to insulate the sensor assembly.
Refer to Fig. 7 and 11 to wire the modulating
water valve
and the sensor to the zone controllel_ Connect the leaving water
temperature
sensor to the controller
using the wiring connec-
tions shown for the SAT sensol_ (NOTE:
The leaving
water
temperature
sensor replaces the SAT sensor in this application.)
Use 18 or 20 AWG wire for all connections.
The water vfdve
actuator housing may be used as a junction
box if the leaving
water temperature
sensor cable is not long enough
and the
sensor cable must be extended to reach the controllel_
For modulating
hydronic
heating
applications,
the default
configuration
must be changed
to properly control the valve.
Refer to the service configuration
table and set the Heating
Loop parameters as follows:
Propollional
Gain = 20.0
Integr_d Gtfin = 0.5
Derivative Gain = 0.0
Start Value = 102.0
Also,
set the Ducted
Heat decision
to YES and set the
Maximum
Duct
Temperature
decision
equal to the design
(maximum)
boiler water temperature
minus 20 degrees, but not
greater than 200 E
Connect
the
Carrier
Communicating
Net-
work Communication
Bus -- The zone
controllers
connect to the bus in a &fisy chain mrangement.
The zone
controller may be installed on a prim_uy bus or on a secon&tq
bus from the primary bus. Connecting
to a secondmy
bus is
recommended.
At 9,600
baud,
the number
of controllers
is limited to
128 zones maximum,
with a limit of 8 systems (Linkage Coor-
dinator configured
for fit least 2 zones). Bus length may not
exceed 4000 ft, with no more than 60 devices on any 1000-ft
section. Optically isolated RS-485 repeaters are required every
1000 ft.
At
19,200 and 38,400
baud,
the number
of controllers
is limited to 128 maximum,
with no limit on the number
of
Linkage Coordinators.
Bus length may not exceed 1000 ft.
The filet zone controller
in a network connects
directly to
the bridge and the othel_ are wired sequentially
in a daisy chain
fashion. Refer to Fig. 31 for an illustration of Communication
Bus wiring.
The Communication
Bus also connects to the zone control-
ler space temperature
sensol: Refer to the Install the Sensors
section for sensor wiring instructions.
COMMUNICATION
BUS WIRE SPECIFICATIONS
-- The
Communication
Bus
wiring
is
field-supplied
and
field-
installed.
It consists
of shielded
three-conductor
cable with
&ain (ground) wire. The cable selected must be identical to the
Communication
Bus wire used for the entire
network.
See
Table 2 for recommended
cable.
Table 2 -- Recommended
Cables
MANUFACTURER
CABLE PART NO.
Alpha
2413 or 5463
American
A22503
Belden
8772
Columbia
02525
NOTE:
Conductors
and drain
wire must be at least 20 AWG
(American Wire Gage), stranded, and tinned copper. Individual con-
ductors must be insulated with PVC, PVC/nylon,
vinyl, Teflon, or
polyethylene.
An aluminum/polyester
100% foil shield and an outer
jacket of PVC, PVC/nyIon, chrome vinyl, or Teflon with a minimum
operating temperature
range of-20
C to 60 C is required.
CONNECTION
TO THE COMMUNICATION
BUS
1. Strip the ends of the red, white, and black conductors
of
the communication
bus cable.
2. Connect one end of the communication
bus cable to the
bridge communication
port labeled COMM2
(if connect-
ing on a secondary
bus).
When connecting
the communication
bus cable, a color
code system for the entire network
is recommended
to
simplify
installation
and checkout.
See Table 3 for the
lecommended
color code.
3. Connect
the other end of the communication
bus cable
to the terminal
block labeled J2A in the zone controller
of the first air terminal.
Following
the color code in
Table
3, connect
the Red
(+) wire
to Terminal
1.
Connect
the White
(ground)
wire
to Terminal
2.
Connect
the Black (-) wire to Terminal
3.
4. Connect additional zone controllers
in a daisy chain fash-
ion, following
the color coded wiring scheme in Table 3.
Refer to Fig. 31.
NOTE:
The communication
bus drain wires (shield) must be
tied together at each zone controllel:
If the communication
bus
is entirely within one building, the lesulting
continuous
shield
must be connected
to ground fit only one single point. If the
communication
bus cable exits from one building
and enters
another building, connect the shields to ground fit a lightning
suppressor
in each building where the cable enters or exits (one
point only).
Table 3 -- Color Code Recommendations
SIGNAL TYPE
+
Ground
COMMUNICATION
PLUG PIN
BUS WIRE COLOR
NUMBER
Red
1
White
2
Black
3
23

Advertisement

Table of Contents
loading

Table of Contents