Heat & Glo SL-5 Installation Manual page 24

Hide thumbs Also See for SL-5:
Table of Contents

Advertisement

Top Vent - Vertical Termination
No Elbow
Note: Use SLP Series
components only.
Note: If installing a vertical vent/termination off the top of
the appliance, the optional vertical termination baffle may
be needed.
V
= 60 ft. Max. (18.3 m)
1
Figure 4.13
24
V
1
Heat & Glo • SL-5, SL-7, SL-9 Installation Manual • 2392-980 Rev. L • 6/17
Exhaust restrictor Instructions
Exhaust restrictors are recommended for these verti-
cally terminated products which have excessive draft.
Exhaust restrictors will compensate for high draft, and
restore visual flame height. If the vent configuration has
a total vertical of 15-60 feet, an exhaust restrictor may
be needed. The exhaust restrictor can be located in the
appliance manual bag.
1. Install the exhaust restrictor over the center of the ex-
haust outlet in the firebox. See Figure 4.14.
2. Center the exhaust restrictor in the open end of the
exhaust outlet and secure through the slots on the
exhaust restrictor with the two 1/4 in. self-tapping
screws provided in the appliance manual bag.
To access the exhaust
openings, remove the
exhaust baffle. To re-
move exhaust baffle, re-
move the two wing nuts.
Top Vent Application
Exhaust restrictor
Rear Vent Application
Exhaust restrictor
Note: Be sure to rein-
stall the exhaust baffle
after exhaust restrictor
installation.
Figure 4.14
EXHAUST BAFFLE

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sl-7lpSl-5lpSl-7Sl-9

Table of Contents