Notes On Possible Severe Personal Injury - Samson 2488 N Mounting And Operating Instructions

Pressure-independent control valve (picv)
Hide thumbs Also See for 2488 N:
Table of Contents

Advertisement

Safety instructions and measures
Referenced standards and regulations
The regulators comply with the requirements of the European Pressure Equipment Directive
2014/68/EU. Devices with a CE marking have an EU declaration of conformity, which in-
cludes information about the applied conformity assessment procedure. This EU declaration
of conformity is included in the Appendix of these instructions (see section 9.2).
Non-electric valve versions whose bodies are not lined with an insulating material coating do
not have their own potential ignition source according to the risk assessment stipulated in
EN 13463-1: 2009, section 5.2, even in the rare incident of an operating fault. Therefore,
such valve versions do not fall within the scope of Directive 2014/34/EU.
Î For connection to the equipotential bonding system, observe the requirements specified in
section 6.4 of EN 60079-14 (VDE 0165 Part 1).
Referenced documentation
The following documents apply in addition to these mounting and operating instructions:
− Mounting and operating instructions for the mounted actuator, e.g. u EB 5857 for
Type 5857 Actuator

1.1 Notes on possible severe personal injury

DANGER
!
Risk of bursting in pressure equipment.
Valves and pipelines are pressure equipment. Improper opening can lead to device
components bursting.
Î Before starting any work on the device, depressurize all plant sections concerned
as well as the valve.
Î Drain the process medium from all the plant sections concerned as well as the
valve.
Î If necessary, install a suitable overpressure protection in the plant section.
Î Wear personal protective equipment.
6
EB 3136 EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

5857