Table 4: Troubleshooting
Malfunction
Flow rate exceeds adjusted set
point
Flow set point not reached.
Control loop hunts.
Note
Contact SAMSON's After-sales Service department for malfunctions not listed in the table
and when the malfunction cannot be remedied as described.
EB 3136 EN
Possible reasons
Leak between seat and plug
Defective operating diaphragm
Control line with needle valve
blocked.
Valve too large for control task
(flow rate) or too small
(differential pressure)
Leak between seat and plug
Incorrect set point range
selected.
Safety device, e.g. pressure
limiter, has been triggered.
Plant differential pressure too
low.
Strainer blocked
Incorrectly installed valve
(direction of flow).
Valve too large for control task

Malfunctions

Recommended action
Remove valve from the pipeline
and clean seat and plug. Con-
tact SAMSON for further action.
Contact SAMSON's After-sales
Service department.
Remove control line and needle
valve. Clean them.
Recalculate K
and contact
VS
SAMSON for further action.
Remove valve from the pipeline
and clean seat and plug. Con-
tact SAMSON for further action.
Check set point range and con-
tact SAMSON for further action.
Check plant. Unlock safety de-
vice.
Compare differential pressure in
the plant with the plant's drag.
Drain and clean filter of the
strainer.
Install the regulator so that the
direction of flow matches the di-
rection indicated by the arrow
on the body.
Recalculate K
and contact
VS
SAMSON for further action.