Startup
The fan runs continuous when placed in the high, medium,
or low position. Use Rover, Trane's installation and service
tool, to change auto defaults.
When the heating output is controlled off, the controller
automatically controls the fan on for an additional 30
seconds. This delay allows the fan to dissipate any residual
heat from the heating source, such as electric heat.
Table 47.
Fan mode operation
Heating Mode
Fan mode
Occupied
Off
Off
Low
Low
Medium
Medium
High
High
Auto
Continuous
Heat default
Cycling off/heat default
(a) Whenever two states are listed for the fan:
The first state (off) applies when there is not a call for heating or cooling.
The second state (varies) applies when there is a call for heating or
cooling.
The heat default is factory configured for low fan speed, and the cool
default is medium.
Table 48. Valid operating range and factory default
setpoints
Setpoint/
parameter
Unoccupied cooling setpoint
Occupied cooling setpoint
Occupied heating setpoint
Unoccupied heating setpoint
Cooling setpoint high limit
Cooling setpoint low limit
Heating setpoint high limit
Heating setpoint low limit
Power-up control wait
Tracer® ZN520 Controllers
Tracer® ZN520 controller is a discrete speed controller that
can be used in a stand-alone application or can
communicate with a building automation system using
LonTalk Communication.
ZN520 Stand-Alone Operation
The factory pre-programs the Tracer® ZN520 with default
values to control the temperature and unit airflow. Use
Tracer® Summit building automation system or Rover™
software to change the default values. For more
information, refer to:
CNT-SVX04*-EN Tracer® ZN520 Unit Controller
Installation, Operation, and Programming Guide
Follow the procedure below to operate the Tracer® ZN520
in a stand-alone operation:
1. Turn power on at the disconnect switch option.
2. Position the fan mode switch to either high, medium,
low, or the auto position.
3. Rotate the setpoint dial on the zone sensor module to
55°F for cooling or 85°F for heating.
106
Cooling Mode
Unoccupied
Occupied
Off
Off
(a)
Off/high
Low
(a)
Off/high
Medium
(a)
Off/high
High
(a)
Off/high
Cool default
(a)
Off/high
Off/cool default
Default
Valid Operating
Setting
Range
85°F
40°F to 115°F
74°F
40°F to 115°F
71°F
40°F to 115°F
60°F
40°F to 115°F
110°F
40°F to 115°F
40°F
40°F to 115°F
105°F
40°F to 115°F
40°F
40°F to 115°F
0 sec
0 sec to 240 sec
The appropriate control valve will actuate assuming the
following conditions:
Room temperature should be greater than 55°F and
less than 85°F .
For a 2-pipe fan-coil unit with an entering water
temperature sensor, the water temperature input is
appropriate for the demand placed on the unit. For
example, cooling operation is requested and cold
water (5° lower than room temperature) flows into the
unit.
Select the correct temperature setpoint.
Note: Select and enable zone sensor temperature
settings to prevent freeze damage to unit.
ZN520 Operation
Fan Mode Switch
Off - Fan is turned off, two-position damper option spring-
returns closed.
Hi, Med, Low - Fan runs continuously at the selected
speed. The two-position damper option opens to an
adjustable mechanical stop position.
Controller
Off - Fan is off; control valves and fresh air damper option
close. Low air temperature detection option is still active.
Auto - Fan speed control in the auto setting allows the
modulating (3-wire floating point) or 2–position control
valve option and three-speed fan to work cooperatively to
meet precise capacity requirement, while minimizing fan
speed (motor/energy/acoustics) and valve position (pump
energy, chilled water reset). As the capacity requirement
increases at low fan speed, the water valve opens. When
the low fan speed capacity switch point is reached, the fan
switches to medium speed and the water valve repositions
to maintain an equivalent capacity. The reverse sequence
takes place with a decrease in required capacity.
Low/Med/High (Continuous Fan) - Fan operates
continuously while control valve option cycles to maintain
setpoint temperature.
Sequence of Operation
Occupancy Modes
The controller operates the fan in the following modes:
Occupied
Unoccupied
Occupied standby
Occupied bypass
Tracer® Summit™ with supply fan control
Occupied
When the controller is in the occupied mode, the unit
attempts to maintain the space temperature at the active
occupied heating or cooling setpoint, based on the
UNT-SVX07J-EN