Danfoss VLT Compact Starter MCD 201 Installation Manual

Ethernet/ip module
Hide thumbs Also See for VLT Compact Starter MCD 201:

Advertisement

ENGINEERING TOMORROW
Installation Guide
EtherNet/IP Module
®
VLT
Compact Starter MCD 201/MCD 202
®
VLT
Soft Starter MCD 500
vlt-drives.danfoss.com

Advertisement

Table of Contents
loading

Summary of Contents for Danfoss VLT Compact Starter MCD 201

  • Page 1 ENGINEERING TOMORROW Installation Guide EtherNet/IP Module ® Compact Starter MCD 201/MCD 202 ® Soft Starter MCD 500 vlt-drives.danfoss.com...
  • Page 3: Table Of Contents

    7 Packet Structures 7.1 Ensuring Safe and Successful Control 7.2 Control Commands (Write Only) 7.3 Status Commands (Read Only) 7.4 Soft Starter Internal Register Address 7.5 Parameter Management (Read/Write) 7.6 Trip Codes MG17M202 Danfoss A/S © 05/2017 All rights reserved.
  • Page 4 Contents EtherNet/IP Module 7.6.1 Internal Fault X 8 Network Design 8.1 Star Topology 8.2 Line Topology 8.3 Ring Topology 8.4 Combined Topologies 9 Specifications Index Danfoss A/S © 05/2017 All rights reserved. MG17M202...
  • Page 5: Introduction

    Starter MCD 201/MCD 202 and VLT Soft Starter MCD 500. The installation guide is intended for use by qualified The EtherNet/IP Module allows a Danfoss soft starter to personnel. connect to an Ethernet network and be controlled or monitored using an Ethernet communication model.
  • Page 6: Symbols, Abbreviations, And Conventions

    Table 1.1 Symbols and Abbreviations Conventions Numbered lists indicate procedures. Bullet lists indicate other information and description of illustrations. Italicized text indicates: • Cross-reference. • Link. • Parameter name. • Parameter group name. • Parameter option. Danfoss A/S © 05/2017 All rights reserved. MG17M202...
  • Page 7: Safety

    Disconnect the soft starter from the mains. • Completely wire and assemble the soft starter, motor, and any driven equipment before connecting the soft starter to AC mains, DC supply, or load sharing. MG17M202 Danfoss A/S © 05/2017 All rights reserved.
  • Page 8 Responsibility or liability is never accepted for direct, indirect, or consequential damage resulting from the use or application of this equipment. Danfoss A/S © 05/2017 All rights reserved. MG17M202...
  • Page 9: Installation

    Connect Ethernet port 1 or port 2 on the module to the network. Apply control power to the soft starter. Illustration 3.2 Removing the EtherNet/IP Option Illustration 3.1 Installing the EtherNet/IP Option MG17M202 Danfoss A/S © 05/2017 All rights reserved.
  • Page 10: Connection

    MCD 201/202 MCD 500 A1, N2: Stop input (Auto-on mode) 17, 18: Stop input 25, 18: Reset input EtherNet/IP Module EtherNet/IP Module RJ45 Ethernet ports RJ45 Ethernet ports Table 4.1 Connection Diagrams Danfoss A/S © 05/2017 All rights reserved. MG17M202...
  • Page 11: Network Connection

    The Ethernet cable must cross the motor and mains cables MAC: 00-02-A2-25-DC-B3 at an angle of 90°. Illustration 4.2 MAC ID Location ≥ 200 mm 90° 3-phase supply Ethernet cable Illustration 4.1 Correct Running of Ethernet Cables MG17M202 Danfoss A/S © 05/2017 All rights reserved.
  • Page 12: Device Configuration

    Connect Ethernet port 1 or port 2 on the module to the Ethernet port of the PC. Apply control power to the soft starter. Start the Ethernet Device Configuration Tool. Illustration 5.1 Entering Network Settings Danfoss A/S © 05/2017 All rights reserved. MG17M202...
  • Page 13 The software searches for connected devices. Illustration 5.3 The Tool Shows the Connected Devices To set a static IP address, click Configure and select Set IP address. Illustration 5.4 Setting a Static IP Address MG17M202 Danfoss A/S © 05/2017 All rights reserved.
  • Page 14: Operation

    The module has obtained an IP address but has not established any network Status connections. Communication has been established. No network connection. Link x Connected to a network. TX/RX x Flashing Transmitting or receiving data. Table 6.1 Feedback LEDs Danfoss A/S © 05/2017 All rights reserved. MG17M202...
  • Page 15: Packet Structures

    3 = Reserved. 2–7 Reserved. Table 7.1 Structures Used for Sending Control Commands to the Soft Starter 1) Ensure that the programmable input is not set to Motor set select before using this function. MG17M202 Danfoss A/S © 05/2017 All rights reserved.
  • Page 16: Status Commands (Read Only)

    0–7 Parameters Total numbers of parameters available in the soft starter. 0–13 Value of the last parameter that was changed, as indicated in byte 12. Changed parameter value 14–15 14–15 Reserved – Danfoss A/S © 05/2017 All rights reserved. MG17M202...
  • Page 17 Parameter list major revision – 0–3 Digital input state For all inputs, 0 = open, 1 = closed. 0 = Start. 1 = Stop. 2 = Reset. 3 = Input A 4–7 Reserved – MG17M202 Danfoss A/S © 05/2017 All rights reserved.
  • Page 18: Soft Starter Internal Register Address

    0 = Negative phase sequence. 1 = Positive phase sequence. 10–15 See trip codes in Table 7.4. 0–13 Average rms current across all 3 phases. Current 14–15 Reserved. 0–9 Current (% motor FLC). Current 10–15 Reserved. Danfoss A/S © 05/2017 All rights reserved. MG17M202...
  • Page 19 0 = Multiply power by 10 to get W. 1 = Multiply power by 100 to get W. 2 = Power is shown in kW. 3 = Multiply power by 10 to get kW. MG17M202 Danfoss A/S © 05/2017 All rights reserved.
  • Page 20: Parameter Management (Read/Write)

    Thermistor circuit Table 7.4 Trip Code Reported in Bytes 2–3 and 17 of the Status Commands ® 1) For VLT Soft Starter MCD 500, time-overcurrent protection is only available on internally bypassed models. Danfoss A/S © 05/2017 All rights reserved. MG17M202...
  • Page 21: Internal Fault

    Table 7.5 Internal Fault Code Associated with Trip Code 104 NOTICE ® ® Only available on VLT Soft Starters MCD 500. For parameter details, see the VLT Soft Starter MCD 500 Operating Guide. MG17M202 Danfoss A/S © 05/2017 All rights reserved.
  • Page 22: Network Design

    Illustration 8.3 Ring Network Topology NOTICE The network switch must support loss of line detection. Illustration 8.2 Line Network Topology Danfoss A/S © 05/2017 All rights reserved. MG17M202...
  • Page 23: Combined Topologies

    Network Design Installation Guide 8.4 Combined Topologies A single network can include both star and line components. Illustration 8.4 Combined Star/Line Network Topology MG17M202 Danfoss A/S © 05/2017 All rights reserved.
  • Page 24: Specifications

    10 Mbps, 100 Mbps (auto-detect) Full duplex Auto crossover Power Consumption (steady state, maximum) 35 mA at 24 V DC Reverse polarity protected Galvanically isolated Certification IEC 60947-4-2 IEC 60947-4-2 ODVA EtherNet/IP conformance tested Danfoss A/S © 05/2017 All rights reserved. MG17M202...
  • Page 25: Index

    Ethernet attribute................. 10 Unintended start..................5 Heat sink..................... 5 Weight...................... 22 Inputs Remote....................5 Installing EtherNet/IP option.............. 7 Intended use..................... 3 IP address..................9, 12, 22 Description..................12 LED......................4 Name....................12 Status....................12 MG17M202 Danfoss A/S © 05/2017 All rights reserved.
  • Page 26 Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.

This manual is also suitable for:

Vlt compact starter mcd 202Vlt soft starter mcd 500

Table of Contents