MCD Modbus Module Instructions
INSTALLATION INSTRUCTIONS: MCD MODBUS MODULE
Order Code: 175G9000
1. Introduction
Danfoss soft starters can be controlled and monitored across an RS485 serial communication
network using the Modbus RTU and AP ASCII protocols.
For users requiring simple control of MCD 200 and MCD 500 soft starters using Modbus RTU or AP
ASCII, the instructions below describe the installation and operation of the Modbus Module.
MCD 3000 soft starters have AP ASCII protocol support built in - see the MCD 3000 Users Manual for
details of message formats. The MCD 3000 supports Modbus RTU control when used in conjunction
with a Remote Operator.
This document describes Modbus and AP ASCII messaging and
the Remote Operator and use it as a Modbus RTU or AP ASCII slave device.
2. Installation
1.
Remove control power and mains supply from the soft starter.
2.
Attach the Modbus Module to the starter as shown.
3.
Apply control power to the soft starter.
Remove the Modbus Module using the following procedure:
1.
Disconnect the RS485 cable from the module.
2.
Remove control power and mains supply from the soft starter.
3.
Push a small flat-bladed screwdriver into the slots at the top and
bottom of the module and depress the retaining clips.
4.
Pull the module away from the soft starter.
MCD 200
CAUTION
Remove mains and control voltage from the soft starter before attaching or removing
accessories. Failure to do so may damage the equipment.
MG.17.F5.02 - VLT® is a registered Danfoss trademark
Appendix A
describes how to connect
MCD 500
Introduction
1

Advertisement

Table of Contents
loading

Summary of Contents for Danfoss MCD 200

  • Page 1 Modbus RTU and AP ASCII protocols. For users requiring simple control of MCD 200 and MCD 500 soft starters using Modbus RTU or AP ASCII, the instructions below describe the installation and operation of the Modbus Module.
  • Page 2 If MCD 500 parameter 3-2 is set to Disable Comms in Remote, the starter will not accept start or stop commands from the serial network (the starter will still accept reset commands and allow status monitoring). MG.17.F5.02 - VLT® is a registered Danfoss trademark...
  • Page 3: Network Status Led

    N.B.!: If communication is inactive, the soft starter may trip if the Communications Timeout function has been set on the module. When communication is restored, the soft starter will require a Reset. MG.17.F5.02 - VLT® is a registered Danfoss trademark...
  • Page 4: Modbus Register

    Multiple Read Serial Protocol Version 40009 Single Write Parameter 1-A (Motor FLC) to: Parameter and Multiple • MCD 500 Par. 20-6 (Pedestal Detect) management Read • MCD 3000 Par. 60 (Min Run Frequency) MG.17.F5.02 - VLT® is a registered Danfoss trademark...
  • Page 5 The numbering of parameter options via serial communications differs slightly from the numbering displayed on the LCP. Numbering via the Modbus Module starts at 0, so for Par. 2-1 Phase Sequence, the options are 1~3 on the LCP but 0~2 via the module. MG.17.F5.02 - VLT® is a registered Danfoss trademark...
  • Page 6: Trip Codes

    Unsupported option (Not available in 6-wire) Starter communication Network communication Internal fault EEPROM fail L1 phase loss L2 phase loss L3 phase loss L1-T1 Shorted L2-T2 Shorted L3-T3 Shorted Time-overcurrent (Bypass overload) Battery/clock Thermistor circuit No trip MG.17.F5.02 - VLT® is a registered Danfoss trademark...
  • Page 7: Modbus Functions

    The Modbus Module supports the following Modbus functions: 03 Read multiple registers 06 Write single register Modbus broadcast functions are not supported. MCD 200 soft starters (including Remote Operator): Read multiple registers 40003 to 40008 Write single register 40002 MCD 500 soft starters:...
  • Page 8: Modbus Error Codes

    Disable control in RMT. Local communication error Communication error between Modbus slave and starter N.B.!: Some of the above codes are different from those defined in the Modbus Application Protocol Specification available on www.modbus.org. MG.17.F5.02 - VLT® is a registered Danfoss trademark...
  • Page 9: Ap Ascii Protocol

    Initiates a stop Reset Resets a trip state Quick stop Initiates an immediate removal of voltage from the motor. Any soft stop settings are ignored. Forced communication trip Causes a communications trip MG.17.F5.02 - VLT® is a registered Danfoss trademark...
  • Page 10: Status Retrieval

    Requests the calculated value of the motor thermal model as a % of motor temperature thermal capacity. The data is four byte decimal ASCII. Minimum value is 0000%. Trip point is 0105%. MG.17.F5.02 - VLT® is a registered Danfoss trademark...
  • Page 11: Calculating The Checksum (Lrc)

    30h plus upper nibble of status byte right shifted by four binary places d4 = 30h plus lower nibble of status byte For example status byte = 1Fh, response is: LRC1 LRC2 MG.17.F5.02 - VLT® is a registered Danfoss trademark...
  • Page 12: Appendix A - Modbus Control Via Remote Operator

    - 7 V to + 12 V Input sensitivity: ± 200 mV Minimum differential output voltage: 1.5 V (with max loading of 54 Ω) 11.5. Using the Remote Operator with MCD 200 MG.17.F5.02 - VLT® is a registered Danfoss trademark...
  • Page 13 Serial Port + GND - - GND + - GND + ~/+ ~/- B8 B7 B6 B10 B11 B1 B2 B3 B6 B7 B8 4-20 mA Supply Voltage Analog Output 18~30 VAC/VDC MG.17.F5.02 - VLT® is a registered Danfoss trademark...
  • Page 14: Programming Procedure

    There is a 20 second timeout when the Remote Operator is in Programming Mode. Programming Mode will automatically close if no input is registered for 20 seconds. Any changes already made will be saved. MG.17.F5.02 - VLT® is a registered Danfoss trademark...
  • Page 15: Programmable Parameters

    Set Par. 6 to a value 10 times greater than the actual motor nameplate FLC (e.g. for actual FLC = 4.6 A, set Par. 6 to 46). Set Par. 9 = 1. MG.17.F5.02 - VLT® is a registered Danfoss trademark...
  • Page 16: Troubleshooting

    Address range ........................... 0 to 31 Data rate (bps) ..................... 4800, 9600, 19200, 38400 Parity ......................None, Odd, Even, 10-bit Timeout ..................... None (off), 10 s, 60 s, 100 s Certification ..........................IEC 60947-4-2 ..........................IEC 60947-4-2 MG.17.F5.02 - VLT® is a registered Danfoss trademark...