AC-53 Rating for Continuous Operation Inside Delta Connection (Bypassed) AC-53 Rating for Bypassed Operation Inside Delta Connection (Non-bypassed/Continuous) AC-53 Rating for Continuous Operation Minimum and Maximum Current Settings Bypass Contactor Main Contactor Circuit Breaker MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 2
Installation with Bypass Contactor Emergency Run Operation Auxiliary Trip Circuit Soft Braking Two Speed Motor 6 Operation The LCP Control Methods Local Control Buttons Displays Temperature Monitoring Screen (S1) Programmable Screen (S2) MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 3
Relays B and C Low Current Flag and High Current Flag Motor Temperature Flag Analog Output A Start/Stop Times Auto-Reset Auto-Reset Delay Secondary Motor Set Display User Programmable Screen Performance Graphs Restricted Parameters MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 4
Alarm Log Trip Log Event Log Counters 9 Troubleshooting Trip Messages General Faults 10 Specifications Accessories Communication Modules PC Software Finger Guard Kit 11 Bus Bar Adjustment Procedure (MCD5-0360C - MCD5-1600C) MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
A motor that has been stopped may start if faults occur in the electronics of the soft starter, or a temporary fault in the supply mains or the motor connection ceases. AUTO-START Use the auto-start feature with caution. Read all the notes related to auto-start before operation. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 6
Equipment containing electrical components may not be disposed of together with domestic waste. It must be collected separately as electrical and electronic waste according to local and cur- rently valid legislation. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
G5 = 1200 A ~ 1600 A Not used IP rating 00 = IP00 20 = IP20 Control voltage CV1 = 24 VAC/VDC CV2 = 110-120 VAC or 220-240 VAC = Not selectable MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
The soft starter may be mounted on its side. Derate the soft starter's rated current by 15%. Soft starters may be mounted side by side with clearance of 50 mm (1.97 inches) on both sides. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
CV1 (24 VAC/VDC) A5, A6 CV2 (110 - 120 VAC) A5, A6 CV2 (220 - 240 VAC) A4, A6 If you are not using a thermistor, do not short terminals 05, 06. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Some units are aluminium bus bars. When connecting power terminations, we recommend cleaning the surface contact area thoroughly (using an emery or stainless steel brush) and using an appropriate jointing compound to prevent corrosion. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 13
The bus bars on models MCD5-0360C - MCD5-1600C can be adjusted for top or bottom input and output as required. For step-by-step instructions on adjusting the bus bars, refer to the supplied insert. Input/Output Input Output MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
For personnel safety, the power terminals on models up to MCD5-0105B are protected by snap-off tabs. When using large cables, it may be necessary to break off these tabs. Models which are internally bypassed do not require an external bypass contactor. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
The fuses can be installed on the input side if required. 4.3 Inside Delta Installation When connecting the MCD 500 in inside delta configuration, always install a main contactor or shunt trip circuit breaker. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
4.4 Current Ratings Contact your local supplier for ratings under operating conditions not covered by these ratings charts. All ratings are calculated at altitude of 1000 metres and ambient temperature of 40° C. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
1319 A 1114 A MCD5-1600C 1600 A 1600 A 1353 A 4.4.2 AC-53 Rating for Bypassed Operation All ratings are calculated at altitude of 1000 metres and ambient temperature of 40° C. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
1187 A 1023 A MCD5-1600C 1600 A 1433 A 1227 A 4.4.4 AC-53 Rating for Continuous Operation All ratings are calculated at altitude of 1000 metres and ambient temperature of 40° C. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
1979 A 1671 A MCD5-1600C 2400 A 2400 A 2030 A 4.4.6 AC-53 Rating for Bypassed Operation All ratings are calculated at altitude of 1000 metres and ambient temperature of 40° C. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
1780 A 1535 A MCD5-1600C 2400 A 2149 A 1841 A 4.4.8 AC-53 Rating for Continuous Operation All ratings are calculated at altitude of 1000 metres and ambient temperature of 40° C. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
If power factor correction is used, a dedicated contactor should be used to switch in the capacitors. Power factor correction capacitors must be connected to the input side of the soft starter. Connecting power factor correction capacitors to the output side will damage the soft starter. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
1000 m altitude. For installations operating outside these conditions, consult your local supplier. These fuse tables contain recommendations only, always consult your local supplier to confirm the selection for your particular appli- cation. For models marked - there is no suitable fuse. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Relay output A 21, 22, 24 Relay output B 33, 34 Relay output C * MCD5-0245C current transformers are located on the output. Bypass terminals are labelled T1B, T2B and T3B. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Motor FLC Par. 1-1 should be set to the motor's rated FLC. Do not add the overload rating as this is computed by the MCD-500. 5.2 AAC Adaptive Acceleration Control AAC Adaptive Acceleration Control is a new form of motor control based on the motor's own performance characteristics. With AAC, the user selects the starting or stopping profile that best matches the load type and the starter automatically controls the motor to match the profile.
Set a start Current Limit (Par. 1-4) sufficiently high to allow a successful start. The first AAC start will be a Constant Current start. This allows the MCD 500 to learn the characteristics of the connected motor. This motor data is used by the MCD 500 during subsequent AAC Adaptive Acceleration Control starts. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
AAC cannot start the motor faster than a direct on-line (DOL) start. If replacing a motor connected to an MCD-500 programmed for AAC starting or stopping, or if the starter has been tested on a different motor prior to actual installation, the starter will need to learn the characteristics of the new motor. To force the MCD-500 into learn mode, adjust par.
1-12 Adaptive Control Gain as follows: If 1-12 is at default setting of 75%, adjust to 76%. If 1-12 is not at default setting of 75%, adjust to 75%. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
50% - 75% of the jog torque in forward direction. To set the jog torque level, use Par. 15-8. Setting Par. 15-8 above 50% may cause increased shaft vibration. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
When connected in inside delta, current imbalance is the only phase loss protection that is active during run. Do not disable current imbalance protection during inside delta operation. Inside delta operation is only possible with mains voltage ≤ 600 VAC. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
These start current requirements are appropriate and typical in most circumstances, However, the performance and start torque re- quirements of motors and machines do vary. For further assistance, contact your local supplier. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 40
Chipper 4.5 x FLC Circular saw 3.5 x FLC Debarker 3.5 x FLC Edger 3.5 x FLC Hydraulic power pack 3.5 x FLC Planer 3.5 x FLC Sander 4.0 x FLC MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Motor terminals 33, 34 Relay output C Parameter settings: • Par. 4-1 Relay A Function • Select Main Contactor - assigns the Main Contactor function to Relay Output A (default value). MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Relay output B 33, 34 Relay output C Parameter settings: • Parameter 4-4 Relay B Function • Select Run - assigns the run output function to Relay Output B (default value). MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Input A Function • Par. 3-3 • Select Emergency Run - assigns Input A to Emergency Run Function Emergency Run) • Par. 15-3 ( • Select Enable - Enables the Emergency Run mode MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Select a name e.g. Low Pressure - assigns a name to Input A. • Par. 3-8 Remote Reset Logic • Select as required e.g. Normally Closed - the input behaves like a normally closed contact. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Par. 4-7 Relay C Function • Select Trip - assigns Trip function to Relay Output C If the MCD-500 trips on supply frequency (Par. 16-5 Frequency ) when the braking contactor KM2 opens, modify the setting of Pars. 2-8 - 2-10.
Line contactor (high speed) 3-phase supply Line contactor (low speed) Motor terminals Star contactor (high speed) Remote low-speed start input Reset contact Remote high-speed start input 21, 22, 24 Relay output B MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 47
Select Trip - assigns Trip function to Relay Output B If the MCD 500 trips on supply frequency (Par. 16-5 Frequency ) when the high-speed start signal (7) is removed, modify the setting of pars. 2-8 - 2-10. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 48
6 Operation MCD 500 Operating Instruction MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
The MCD 500 can also be set to allow local control only or remote control only, using par. 3-1 If par. 3-1 is set to Remote Control Only , the OFF button is disabled and the motor must be stopped by remote control or via the serial communication network. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
6.3 Local Control Buttons If Par. 3-1 is set to LCL/RMT Anytime or LCL/RMT When OFF, the Hand On and Auto On buttons are always active. If the MCD-500 is in Auto On mode, pressing the Hand On button will enter Hand On mode and start the motor.
The current screen shows real-time line current on each phase. Ready 000.0A 000.0kW Phase currents 000.0A 000.0A 000.0A 6.4.5 Frequency Monitoring Screen (S5) The frequency screen shows the mains frequency as measured by the soft starter. Ready 000.0A 000.0kW 00.0Hz MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
The date/time screen shows the current system date and time (24 hour format). For details on setting the date and time, see Ready 000.0A 000.0kW YYYY MMM DD HH:MM:SS 6.4.9 SCR Conduction Bargraph The SCR conduction bargraph shows the level of conduction on each phase. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
The newest information is displayed at the right hand edge of the screen. The graph can be paused to analyse data by pressing and holding the OK button. To re-start the graph, press and hold OK. 000.0 A 0-400% MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 54
7 Programming MCD 500 Operating Instruction MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
If a user attempts to change a parameter value or access the Main Menu when the adjustment lock is active, an error message is displayed: Access Denied Adj Lock is On MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Motor Temp Flag Start/Stop Timers Auto-Start Type Auto-Start Time Auto-Stop Type Auto-Stop Time Display Language User Scrn Top L User Scrn Top R User Scrn Btm L User Scrn Btm R MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Locked Rotor Time 20 seconds Locked Rotor Time 30 seconds Compressor Screw Motor FLC Start Mode Adaptive Control Adaptive Start Profile Constant Acceleration Start Ramp Time 10 seconds Current Limit 400% MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
• Press OK or BACK to move the cursor. ▲ ▼ • Use the button to select the parameter number. Parameter shortcut Please enter a Parameter number 01-01 MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
The parameters in Primary Motors Settings configure the soft starter to match the connected motor. These parameters describe the motor's operating characteristics and allow the soft starter to model the motor's temperature. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 60
Set for a period slightly longer than required for a normal healthy start. A setting of 0 disables excess start time protection. 20 secs* [0:00 - 4:00 (min:secs)] Set as required. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Brake uses DC injection to actively slow the motor. See in chapter for more details. 1-15 Brake Torque Range: Function: 20%* [20 - 100%] Sets the amount of brake torque the MCD 500 will use to slow the motor. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Slows the MCD 500's response to undercurrent, avoiding trips due to momentary fluctuations. 7.6.3 Instantaneous Overcurrent The MCD 500 can be configured to trip if the average current of all three phases exceeds a specified level while the motor is running. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Slows the MCD 500's response to frequency disturbances, avoiding trips due to momentary fluctu- ations. If the mains frequency drops below 35 Hz or rises above 75 Hz, the starter will trip immediately. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
LCP. When the input is open, the starter is in local mode and can be controlled via the LCP. When the input is closed, the starter is in remote mode. The HAND ON and AUTO ON buttons are MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 65
The state of the input is ignored until the initial delay has elapsed. 3-8 Remote Reset Logic Option: Function: Selects whether the MCD 500's remote reset input (terminals 25, 18) is normally open or normally closed. Normally Closed* Normally Open MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
The relay closes when the motor temperature flag activates (Par. 4-12 4-5 Relay B On Delay Range: Function: 0 secs* [0:00 - 5:00 (min:secs)] Sets the delay for closing Relay B. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
The flag can signal the situation to external equipment via one fo the programmable outputs. 4-12 Motor Temp Flag Range: Function: 80%* [0% - 160%] Sets the level at which the motor temperature flag operates, as a percentage of the motor's thermal capacity. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
The soft starter will auto-start at the time programmed in Par. 5-2. 5-2 Auto-Start Time Range: Function: 1 min* [00:01 - 24:00 (hrs:min)] Sets the time for the soft starter to auto-start, in 24 hour clock format. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
[100% - 700% FLC] Sets the level of the kickstart current. 7-8 Kickstart Time-2 Range: Function: 0000 [0 - 2000 msecs] Sets the kickstart duration. A setting of 0 disables kickstart. msecs* MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 71
Selects which profile the MCD 500 will use for an AAC adaptive acceleration control soft stop. Early Deceleration Constant Deceleration* Late Acceleration 7-15 Brake Torque-2 Range: Function: 20%* [20 - 100%] Sets the amount of brake torque the MCD 500 will use to slow the motor. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
The starter's operating state (starting, running, stopping or tripped). Only available for “Top L” and “Btm L”. Motor Current The average current measured on three phases. Motor pf The motor's power factor, measured by the soft starter. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
To re-start the graph, press and hold OK. 8-6 Graph Timebase Option: Function: Sets the graph time scale. The graph will progressively replace the old data with new data. 10 secs* 30 secs 1 min MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Selects whether the soft starter will permit emergency run operation. In emergency run, the soft starter will start (if not already running) and continue to operate until emergency run ends, ignoring stop commands and trips. Emergency run is controlled using a programmable input. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 75
Range: Function: Jog Operation 50%* [20% - 100%] Sets the torque level for jog operation. See the section for more details. Setting Par. 15-8 above 50% may cause increased shaft vibration. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
16-10 Starter/Comms • 16-11 Network/Comms • 16-12 Battery/Clock Trip Starter* Warn and Log Log Only 7.15 Factory Parameters These parameters are restricted for Factory use and are not available to the user. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
OK to load/save the selection or exit the screen. Load Defaults When the action has been completed, the screen will briefly display a confirmation message, then return to the status screens. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Protection Action setting (parameter group 16). Press BACK to return to the simulation list. ▲ ▼ to select another simulation, or press BACK to re- turn to the Main Menu. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
8.8 Temp Sensors State This screen shows the state of the motor thermistor. Temp Sensors State The screen shot shows the thermistor state as O (open). Thermistor: O S = shrt H=hot C=cld O=opn MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Motor kWh (lifetime and since counter last reset) • Number of times the thermal model has been reset The resettable counters (hours run, starts and motor kWh) can only be reset if the correct access code is entered. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 81
Press OK to view details. To reset a counter, press OK then enter the access code. Select Reset, then press OK to confirm. To close the counter and return to the Alarm Logs, press BACK. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 82
9 Troubleshooting MCD 500 Operating Instruction MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
If the MCD 500 is connected to a generator set supply, the generator may be too small or could have a speed regulation problem. Related Pars.: 2-8, 2-9, 2-10, 16-5 MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 84
Network Comms The network master has sent a trip command to the starter, or there may be a network communication problem. Check the network for causes of communication inactivity. Related Pars.: 16-11 MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 85
(shafts, belts or couplings), or a pump running dry. Related Pars.: 2-4, 2-5, 16-3 Unsupported Option The selected function is not available (e.g. jog is not supported in inside delta configuration). Related Pars.: None MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
AAC adaptive acceleration control, DC brake and - These features are only available with in-line installation. If the MCD 500 is installed inside Jog functions not working delta, these features will not operate. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 87
- The EEPROM may be faulty on the Main Control PCB. A faulty EEPROM will also trip the soft Par. Out of Range starter, and the LCP will display the message . Contact your local supplier for advice. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 88
10 Specifications MCD 500 Operating Instruction MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
IP20 & NEMA, UL Indoor Type 1 MCD5-0131B - MCD5-1600C IP00, UL Indoor Open Type Operating temperature -10° C to 60° C, above 40° C with derating Storage temperature - 25° C to + 60° C MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
● ● Upload parameter settings Download parameter set- ● ● tings The PC software available from Danfoss's website is: • WinMaster: VLT ® Soft Starter software for control, configuration and management • ® MCT10: VLT software for configuration and management.
All units are manufactured with input and output bus bars at the bottom of the unit as standard. The input and/or output bus bars can be moved tot he top of the unit if required. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 94
3. Place the CT assembly over the input bus bars and screw the assembly to the body of the starter (see note). 4. Run all wiring to the side of the starter and secure with cable ties. MG.17.K2.02 - VLT ® is a registered Danfoss trademark...
Page 95
MCD5-0360C - MCD5-0930, the CTs must be placed on an angle (the left hand legs of each CT will be on the top row of holes and the right hand legs will be on the bottom tabs). MG.17.K2.02 - VLT ® is a registered Danfoss trademark...