Configuring S7F/FH hardware
6.3 Communications module parameters/Networks
Requirements for using PROFINET with F Systems
The PROFIsafe version V2 required for fail-safe communication via PROFINET is available
in F Systems as of V6.0.
The following components are required to use PROFINET with F Systems:
Recommended software requirements:
● PCS 7 V8.0 SP2 or higher
● S7 F Systems V6.1 SP1 or higher
● S7 F Systems Lib V1.3 or higher
● S7 F Configuration Pack V5.5 SP11 or higher
Hardware requirements:
● CPU (CPU 412-5H, CPU 414-5H, CPU 416-5H, CPU 417-5H or CPU 410-5H)
● I/O modules:
– SM 326F, DI 24xDC24V (6ES7 326-1BK02-0AB0)
– SM 326F, DO 10xDC24V/2A, P-switching (6ES7 326-2BF10-0AB0)
– SM 326F, DO 8xDC24V/2A, P-M-switching (6ES7 326-2BF41-0AB0)
– SM 336F, AI 6x0/4...20mA HART (6ES7 336-4GE00-0AB0)
Note
Before you use the fail-safe devices make sure that they support PROFIsafe V2 mode
(F_Par_Version = 1) on PROFINET IO as well as in the downstream networks (PROFINET
IO or PROFIBUS DP).
The set PROFIsafe mode of the device is documented in the hardware printout.
40
Compendium Part B - Process Safety (V8.2)
Operating Manual, 07/2016, A5E35031794-AB