Parameter assignment for shutdown behavior

From S7 F Systems V6.0 with S7 F Systems Lib V1_3 and higher, the shutdown behavior in
the event of an F-STOP is defined in the "Safety Program" dialog using the "Shutdown
behavior" button.
You can use the "Shutdown behavior" dialog to select how the safety program should
behave when an error is detected (in other words, in the event of an F-STOP):
● "Complete shutdown":
All F-shutdown groups associated with a safety program are shut down the first time an
error is detected in an F-shutdown group.
● "Acc. to parameter assignment at F_SHUTDN":
Block F_SHUTDN is located in the @F_ShutDn chart. At the SHUTDOWN input, you can
choose from:
– "Partial":
– "Full":
Compendium Part B - Process Safety (V8.2)
Operating Manual, 07/2016, A5E35031794-AB
The faulty F-shutdown group(s) is (are) shut down the first time an error is detected in
an F-shutdown group (partial shutdown).
or
Configuring the safety program
7.4 F-STOP
101