Parameters Of The Counting Mode - Siemens Simatic ET 200MP Manual

Digital input module (6es7521-1bl00-0ab0)
Hide thumbs Also See for Simatic ET 200MP:
Table of Contents

Advertisement

Parameters/address space
4.1 Parameter
4.1.3

Parameters of the Counting mode

Parameters of the DI 32x24VDC HF Count in the Counting mode
If you want to use the module for counting, you need to set the module parameters as DI
32x24VDC HF Count. For channels 0 and channel 1, the following parameter settings are
then possible. For channels 2 to 31, the parameter settings apply as with the DI 32x24VDC
HF, , see section Parameters DI mode (Page 16).
Table 4- 2
Settable parameters and their defaults in the Counting mode
Parameter
Diagnostics
No
supply voltage L+
Wire break
Input delay
Hardware interrupt
Set output DQ
Edge selection
High counting limit
Comparison value
Start value
Behavior when a count-
ing limit is exceeded
* If you enable diagnostics for multiple channels, you will receive an alarm storm on failure of the supply voltage because
each enabled channel will detect this fault.
You can prevent this message burst by enabling diagnostics for one channel only.
** Comparison value or start value must be less than or equal to the value for the high counting limit.
18
Range of values
Default setting
Yes/No
No
Yes/No
No
0.05 ms, 0.1 ms,
3.2 ms;
0.4 ms, 1.6 ms,
for isochronous
3.2 ms, 12.8 ms,
mode 0.05 ms
20 ms
(cannot be
changed)
Disable
Disable
Comparison event
occurred for DQ
Between a
Between a compar-
comparison
ison value and the
value and the
high counting limit
high counting
Between a compar-
limit
ison value and the
low counting limit
On rising edge
On rising edge
On falling edge
On rising and fall-
ing edge
0 ... 4294967295
4294967295
0 ... 4294967295**
1
0 ... 4294967295**
0
Stop counting
Stop counting
Continue counting
Parameter
Range of effectiveness with configura-
reassign-
tion software, e.g. STEP 7
ment in
Integrated in the
RUN
hardware catalog as of
STEP 7, V13 SP1 with
HSP 0118 or GSD file
PROFINET IO
Yes
Channel*
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
DI 32x24VDC HF digital input module (6ES7521-1BL00-0AB0)
Manual, 09/2016, A5E03485935-AF
GSD file
PROFIBUS DP
---
---
---
---
---
---
---
---
---
---

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500

Table of Contents