TPPR
Protective Earth
Shielding
Figure 44.
TPPR
Protective Earth
Figure 45.
Note:
Cable shielding (screening) shall be connected to the TPPR enclosure's common earth point only, and both shall be fully
isolated from all other metal bodies.
Cable armour and/or steel conduit and/or metal junction boxes and/or metal sensor bodies must be connected to protective
earth (ground) in the field and shall be kept fully isolated from contact with cable shielding (screening) and from contact with
TPPR enclosures or metal enclosure glands.
Long cable runs should be earthed in the field at regular intervals but be careful to avoid earth (ground) loops.
Part. No. 2400M2501_6
MODBUS INSTALLATION
Shielding with Metal Armour, Plastic Junction Box and Plastic Sensor Body
Shielding with no armour, Plastic Junction Box and Plastic Sensor Body
Armour
Shielding
37
Sensor
Junction Box
Shielding
Sensor
Junction Box
Touchpoint Pro
Technical Handbook