Honeywell Touchpoint Pro Technical Handbook page 178

Hide thumbs Also See for Touchpoint Pro:
Table of Contents

Advertisement

TECHNICAL SPECIFICATIONS
21.4.6 Uninterruptible Power Supply Module (UPS)
Description
Input Current
Output Voltage
Output Current
Allowed Batteries
Dimension
Operating Temperature
Operating Humidity
De–rating 60 °C to 70 °C
Storage Conditions
21.4.7 Backup Batteries
Description
Battery type
Dimensions
Weight
Operating Temperature
Operating Humidity
Storage conditions
Storage Lifetime without re–
charge
Ingress Protection
Input Voltage (charging)
Output Voltage (when supplying)
Maximum Input Current
Maximum Output Current
Environmental Protection Class
Fuse type (inline)
Current Limit Protection
Maximum Altitude
Part. No. 2400M2501_6
23.3 VDC – 30 VDC
70 mA typical internal current consumption
Current consumption for battery charging in constant current mode at 24V input
1.7 A typical at battery selector position <10Ah
3.4 A typical at battery selector position >10Ah
DC 24 V (nominal) in Normal Operation
Adjustable in Battery Operation
Max. 25 A in Normal Operations min. 20 A in Battery Operation
2 x 12 V
3.9 Ah – 130 Ah
VRLA (sealed lead acid) type
46 mm x 124 mm x 127 mm (W x H x D)
–40 °C to +70 °C
5 to 95 %RH (non–condensing)
0.5 A / ºC
–40 °C to +85 °C, 5 to 95 %RH (non-condensing)
2 x 12 V (24 V nominal) sealed lead acid batteries
FIAMM 12 V 12 Ah FG21202 or 12 V 27 Ah FG22703
395 mm x 300 mm x 215 mm (W x H x D)
15.7 kg (12 Ah) / 25 kg (27 Ah)
–20 °C to +45 °C
10 to 90 %RH non condensing
–20 °C to +40 °C, 10 to 90 %RH
18 months at <5 °C, 6 months at 25 °C, 3 months at 30 °C, 2 months at 40 °C
IP20, NEMA Code 1
25 VDC to 28 VDC (UPS Supervised)
20 VDC to 28 VDC (dependent on charge level)
3 A
20 A
Equipment Class III, Installation Cat 2, Pollution Degree 2
Bussman 20 A Fast Acting Type ABC–20–R – 1¼' x ¼' Ceramic Tube
Double pole circuit breaker / Isolator, 20 A
2000 m (6562 feet)
171
Touchpoint Pro
Technical Handbook

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tppr

Table of Contents