3 Installation and Wiring
Forced Air Circulation (with Fan in Closed Panel)
NA Unit
Forced Circulation
Room Cooling (Cooling the Entire Room Where the Control Panel Is Located)
3
Cooler
NA Unit
Control panel
Room Cooling
Low Temperatures
The NA Unit may not start normally if the temperature is below 0°C when the power is turned ON.
Maintain an air temperature of at least approximately 5°C inside the panel, by implementing measures
such as installing a low-capacity space heater in the panel. Alternatively, leave the NA Unit power ON to
keep the NA Unit warm.
3-5-2
Humidity
Rapid temperature changes can cause condensation to occur, resulting in malfunctioning due to
short-circuiting. When there is a possibility of this occurring, take measures against condensation, such
as leaving the NA Unit power ON at night or installing a heater in the control panel to keep it warmer.
Control panel
Moisture absorber
NA Unit
Power ON
Heater
Examples of Measures against Condensation
3 - 15
NA-series Programmable Terminal Hardware User's Manual (V117)