Target phase for pulse output/ alarm (OUT1 OUT2)
*It skips when [AL-VU, AL-CU, AL-PD, Cnt1, Cnt2, PL-L] is selected for unit for pulse output.
Select phase to monitor in order to judge the output.
It differs according to the setting unit and phase/wire systems.
Press <ITEM/△>, <SHIFT/▽> to select.
Set unit
Integral value
AL-P, AL-Q, AL-S
(Power alarm)
AL-S (Stand-by alarm)
AL-UC, AL-uC, AL-CH,
AL-CT,AL-CD
AL-PF, AL-oF, AL-uF,
AL-C
AL-uV, AL-oV,
AL-MS, AL-VH, AL-VT
*Selecting [All], it output when one of voltage of phase1, phase2 or phase3 exceeds (or falls below) the
threshold.
Selecting [total], it output when total voltage of phase1, phase2 and 3 exceeds (or falls below) the
threshold.
[Setting window display] example of OUT1
total
All
Phase-n
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
total, Phase1, Phase2, Phase3
・For 3P3W, it fixes total. Setting window is skipped.
total, All, Phase1, Phase2, Phase3
・For 3P3W, it fixes total. Setting window is skipped.
All, Phase1, Phase2, Phase3
All, Phase1, Phase2, Phase3
・For 3P3W, it can't be selected. Setting window is skipped.
All, Phase1, Phase2, Phase3
・For 3P4W: All*, Phase1, Phase2, Phase3, Phase-n
*Except Phase-n
All, Phase1, Phase2, Phase3
・For 3P3W: All, Line1-2, Line2-3, Line3-1
Phase1
Line 1-2
Set list
(initial: total)
(initial: total)
(initial: All)
(initial: All)
(initial: All)
(initial: All)
Phase2
Line 2-3
36
(initial: All)
(initial: All)
Phase3
Line 3-1