Panasonic KW9M User Manual page 16

Eco-power meter advanced type
Hide thumbs Also See for KW9M:
Table of Contents

Advertisement

The input voltage to each terminal is as follows.
Terminal
Phase and wire system
Power
Single-phase two-wire
supply
Single-phase two-wire
Measured
Single-phase three-wire
voltage
input
Three-phase three-wire
Three-phase four-wire
◆Applicable wire (Crimp-type terminal is recommended.) ・Stripping length: 7 to 8mm
・Power supply/Measured voltage/RS485 communication
Terminal block: A
Screw size: M2.5
Tightening torque: 0.4 to 0.5N・m
Sectional area
single /stranded wire 0.5 to 4mm
・for 2pcs.
single/stranded wire 2pcs.×0.5 to 2mm
*Use shielded wire for RS485 communication.
・Output/Input
Terminal block: C
Screw size: M2
Tightening torque: 0.2 to 0.25N・m
Sectional area:
single /stranded wire 0.5 to 1.5mm
・CT Input (Measured current)
Terminal block: B
Screw size: M2.5
Tightening torque: 0.4 to 0.5N・m
Sectional area:
single /stranded wire 0.5 to 4mm
*Use applicable wire according to the measured current.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Terminal No.
1 - 2
85-264V AC [ 85-264V
(L+ - N-)
100-300V DC [100-300V
3 - 6
0-500VAC [0-500V
(V1-Vn)
3 - 5 - 6
0-500VAC [0-500V
(V1-V3-Vn)
0-250VAC [0-250V
3 - 5 - 6
0-500VAC [0-500V 3
(V1-V3-Vn)
3 - 4 - 5 - 6
0-500VAC [0-500V 3
(V1-V2-V3-Vn)
0-289VAC [0-289V 3N
2
(AWG20 to12)
2
(AWG20 to 14)
2
(AWG20 to16)
2
(AWG20 to12)
9
Input voltage
]
]
]
(L-L)
:3W]
(L-L)
:3W]
(L-N)
]
(L-L)
]
(L-L)
]
(L-N)

Hide quick links: