Power input type
Select input type to use for demand measurement, current measurement or pulse input.
'CT'; Use current measurement via CT for demand measurement.
'PM'; Use pulse input for demand measurement.
Count value by pulse input2 is used for power input.
Pulse type
Select pulse type to input.
'kWh'; Set electric power value per 1-pulse directly.
'PULSE'; Use pulse constant value of pulse output device to use.
Pulse rate (electric power conversion)
Set electric power value per 1-pulse.
Pulse constant value
Select pulse constant value input by an outer pulse detector.
Check and select the pulse constant value of using pulse detector.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
*It is only when [30min] is selected for power demand type.
*It is only when [PM] is selected for power input type.
Press <ITEM/△>, <SHIFT/▽> to set.
[Set range] 0.001 to 100.000 [kWh]
Increase
Decrease
* It is only when [PULSE] is selected for pulse type.
Press <ITEM/△>, <SHIFT/▽> to select.
[Set list] CT(current measurement),
PM(Pulse input)
Press <ITEM/△>, <SHIFT/▽> to select.
[Set list] kWh, PULSE (initial: kWh)
* It is only when [kWh] is selected for pulse type.
Press <ITEM/△>, <SHIFT/▽> to select.
[Set list] 50000(pulse/kWh), 2000(pulse/kWh)
31
(initial: CT)
(initial: 50000)