[Set list] integral value (kWh/1pulse): 0.0001, 0.001, 0.01, 0.1, 1, 10, 100,
AL-S (stand-by alarm), AL-uV (under voltage alarm), AL-oV (over voltage alarm),
AL-MS (power interruption alarm), AL-uC (under current alarm), AL-C (current alarm),
AL-P (active power alarm), AL-Q (reactive power alarm), AL-S (apparent power alarm),
AL-PF (power factor alarm), AL-oF (over frequency alarm), AL-uF (under frequency alarm),
AL-VH (voltage harmonics alarm), AL-CH (current harmonics alarm),
AL-VT (voltage THD alarm), AL-CT (current THD alarm), AL-VU (voltage unbalancing alarm),
AL-CU (current unbalancing alarm), AL-PD (Power demand alarm),
AL-CD (current demand alarm), Cnt1 (count output), Cnt2 (count output), PL-L (level output)
・When one of AL-uV(under voltage alarm), AL-oV(over voltage alarm), AL-uC (under current alarm),
AL-C(current alarm) is set, alarm is output according to the settings of under voltage, over voltage,
under current, over current.
・When AL-MS(power interruption alarm) is set, alarm is output when it detects voltage under 5% of
rated voltage.
・When PL-L(level output) is set, when the designated data register is 1, it output.
It is necessary to control by outer device. Write 1 (output ON) or 0 (output OFF) to the designated data
register (OUT1:DT00005, OUT2:DT00006).
* Notes for selecting integral value
Select unit for pulse output so that pulse is less than 1-pulse for 1 second.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
* [AL-PD] is skip when [Peak] is selected for
Power demand type.
35
(initial: 0.001)