Johnson Controls TEC2627-2 Installation Instructions And Operators Manual page 21

Tec26x7-2 series bacnet ms/tp networked thermostats with two outputs
Table of Contents

Advertisement

Table 5: Installer Configuration Menu (Part 3 of 4)
Parameter
Description and Default
Appearing
on Display
SeqOpera
Determines the sequence of
operation.
Default: 1
Unocc HT
Sets the Unoccupied Heating
setpoint value.
Default: 62.0°F/16.5°C
Unocc CL
Sets the Unoccupied Cooling
setpoint value.
Default: 80.0°F/26.5°C
Heat max
Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default: 90.0°F/32.0°C
Cool min
Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default: 54.0°F/12.0°C
Set type
Provides the option of temporarily
changing the heating or cooling
setpoint by pressing the UP/DOWN
arrow keys.
Default: permnent
TOccTime
Sets the duration of the Temporary
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
an Override Function enabled in
the Main User Menu (when the
thermostat is in the Unoccupied
mode)
a temporary heating or cooling
setpoint
Default: 2.0 hrs
DoorTime
Engages the Unoccupied mode if
the door stays open minimally for
the time specified.
Default: 2.0 min
Deadband
Sets the minimum deadband
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C°
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions
Selection Options
(0): Cooling Only (Off-Cool). The default is Cool.
(1): Heating Only (Off-Heat). The default is Heat.
(2): Cooling and Reheat (Off-Auto-Heat-Cool). The default is Heat.
(3): Heating and Reheat (Off-Heat). The default is Heat.
(4*): Cool/Heat Four-Pipe (Off-Auto-Heat-Cool). The default is Heat.
(5*): Cool/Heat Four-Pipe and Reheat (Off-Auto-Heat-Cool). The
default is Heat.
* Selection option (4.0) for Out1Conf only. (See Out1Conf parameter
earlier in this table.)
Note: Choose the selection option (0): Cooling Only when using a
changeover sensor to allow changeover to occur between
Cooling Only and Heating Only. Choose the selection
option (2): Cooling and Reheat when using a changeover
sensor to allow changeover to occur between Cooling and
Reheat and Heating and Reheat.
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
(temporar): Local changes to the heating or cooling setpoints are
temporary, and remain effective for the specified TOccTime.
(permnent): Local changes to the heating or cooling setpoints are
permanently stored in the thermostat memory.
Range: 0.0 to 24.0 hrs in 1-hour increments
Range: 1.0 to 10.0 min
Range: 2.0F°/1.0C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C°
increments)
Note: When adjusting the
temperature, press
the UP/DOWN
arrow keys to
change the
temperature in
0.5F°/0.5C°
increments; press
and hold the
UP/DOWN arrow
keys to change the
temperature in
5.0F°/5.0C°
increments.