Table 2: MS/TP Bus Objects (Part 2 of 4)
Point Name
Cooling (BO1 and BO2) Valve Status
5
(TEC2627-2 Model)
5, 6
BI1 Status
5, 6
BI2 Status
5, 6
UI3 Status
5
Window Alarm
5
Filter Alarm
5
Service Alarm
Occupied Heat Setpoint
Occupied Cool Setpoint
Unoccupied Heat Setpoint
Unoccupied Cool Setpoint
3
Keypad Lockout
3
BI1 Configuration
3
BI2 Configuration
3
UI3 Configuration
3
Menu Scroll
3
Temperature Scale
10
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions
Thermostat Point
(Type/Address)
MSV 67
BI 62
BI 63
BI 64
BI 58
BI 59
BI 60
3, 7
AV 49
3, 7
AV 50
AV 51
3, 7
3, 7
AV 52
MSV 40
MSV 16
MSV 17
MSV 18
BV 19
BV 21
Range
For On/Off Control:
1 = Open
2 = Closed
For Floating Control:
1 = Stopped
2 = Opening
3 = Closing
0 = Deactivated
1 = Activated
0 = Deactivated
1 = Activated
0 = Deactivated
1 = Activated
0 = Off
1 = On
0 = Off
1 = On
0 = Off
1 = On
40.0°F/4.5°C to
90.0°F/32.0°C
54.0°F/12.0°C to
100.0°F/37.5°C
40.0°F/4.5°C to
90.0°F/32.0°C
54.0°F/12.0°C to
100.0°F/37.5°C
1 = Level 0
2 = Level 1
3 = Level 2
4 = Level 3
5 = Level 4
6 = Level 5
1 = None
2 = Rem NSB
3 = Motion NO
4 = Motion NC
5 = Window
1 = None
2 = Door Dry
3 = Override
4 = Filter
5 = Service
1 = None
2 = COC/NH
3 = COC/NC
4 = COS
5 = SS
0 = No Scroll
1 = Scroll Active
0 = °C
1 = °F