This section briefly describes special programming considerations for the NCC
associated with the Ethernet fiber switches. Please refer to the NCC Manual, P/N
315-049679, for more detailed information.
NCCs are located in the Fire Command Centers and are connected to the Fiber Optic
switch at the FCC. There are a maximum of four NCCs in the entire complex for
legacy system, and a maximum of two NCCs for FVNET network system.
Example of IP address range is 192.168.1.1 – 192.168.1.64
XNET Address Node ID range is 1-64
NCC database requires Node IDs from all nodes in all XLS systems
NCC requires Node IDs and IP address information from:
- NCC
- Fiber Optic Switch
To setup the IP address of the NCC execute the following steps:
From the desktop click Start->Network Connections->Local Area Connection.
From the Local Area Connections Status window click Properties.
From Local Area Connections Properties window click on Internet Protocol
then properties.
From Internet Protocol Properties window choose Use the following IP
address and choose and IP address in the range 192.168.1.60 - 192.168.1.63
with the subnet mask of 255.255.255.0.
23
P/N 315-050537-3