F0
NA
H3
NA
LED blinks
eight times
H8
then off for 3
seconds.
LED blinks
five times
E5
then off for 3
seconds.
E8
NA
Low refrigerant
charge due to leak
or defect.
Compressor
overload protection.
Condensate water
overflow protection.
Water reservoir is
full.
Overload
malfunction.
Overload
protection.
Find leak and repair.
Recharge refrigerant.
The coils are dirty or the air inlet or outlet is
blocked. Clean coils and/or move/remove
obstructions.
Fan is not running or set too low. Increase fan
speed or replace fan if defective.
Compressor is defective. Replace compressor.
Refrigerant leak. Repair leak and recharge system.
Restriction in refrigeration system. Locate and clear
restriction, then recharge refrigerant.
Water flinger motor defective or fly wheel
obstructed. Clear obstructions, repair alignment of
motor or replace if defective.
Water reservoir full. Drain water from unit.
Level switch stuck or being interfered with. Remove
any obstructions from water tray and/or unstick
switch. Make sure switch is free to move as water
level changes.
Loose or disconnected switch wiring. Repair
connections.
Level switch is defective. Replace switch.
Main PCB is defective. Replace PCB.
Unstable power supply voltage or supply voltage
too low. Requires certified electrician to adjust
supply voltage to within proper operating
parameters.
The coils are dirty or the air inlet or outlet is
blocked. Clean coils and/or move/remove
obstructions.
Fan is not running or set too low. Increase fan
speed or replace fan if defective.
Compressor is defective. Replace compressor.
Restriction in refrigeration system. Locate and clear
restriction, then recharge refrigerant.
The coils are dirty or the air inlet or outlet is
blocked. Clean coils and/or move/remove
obstructions.
17