6.3.4 Refrigerant Line Leak Test
IOM
IOM
Test for leak
Pressurize the refrigerant lines and
evaporator coil to 350-400 PSIG using dry
nitrogen (Fig. 19). The nitrogen pressure
must be maintained for few minutes.
If pressure decay is observed,
it is an indication of leak(s).
Check for leaks by using a soap
solution at each brazed joint (Fig. 20).
6.3.5 Refrigerant Line Insulation
The Vapor Line must always
be insulated (Fig. 21).
DO NOT allow the liquid line and
vapor line to come in direct (metal
to metal) contact to each other.
W415-1395 / C / 06.26.2017
19
20
21