Convenience Outlets - Bryant 580J Series Installation Instructions Manual

Single package rooftop, gas heating/electric cooling vertical air flow unit with puron (r-410a) refrigerant
Table of Contents

Advertisement

CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to
electrical components. Such operation would invalidate
any applicable Bryant warranty.
Units Without Disconnect Option
TB1
11
12
Disconnect
per NEC
L1
L2
208/230-3-60
460-3-60
575-3-60
Units With Disconnect Option
Factory
Wiring
T1
T2
Optional
Disconnect
Switch
L1
L2
L1
L2
Fig. 26 - - Power Wiring Connections
Convenience Outlets —
WARNING
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Lock- - out and tag- - out this switch, if necessary.
Two types of convenience outlets are offered on 580J units:
Non- - powered and unit- - powered. Both types provide a
125- - volt GFCI (ground- - fault circuit- - interrupter) duplex
receptacle rated at 15- - A behind a hinged access cover,
located on the corner panel of the unit. See Fig. 27.
Equip
GR Lug
13
L3
Ground
(GR)
Equip
GR Lug
T3
L3
Ground
L3
(GR)
C13662
Control Box
Access Panel
Electric
Disconnect
Switch
Convenience
Outlet
Fig. 27 - - Convenience Outlet Location
Installing
Weatherproof
while-in-use cover for the factory-installed convenience
outlets is now required by UL standards. This cover cannot
be factory-mounted due its depth; it must be installed at unit
installation. For shipment, the convenience outlet is covered
with a blank cover plate.
The weatherproof cover kit is shipped in the unit's control
box. The kit includes the hinged cover, a backing plate
and gasket.
DISCONNECT
ALL
POWER
CONVENIENCE OUTLET. LOCK- - OUT AND TAG- - OUT
ALL POWER.
Remove the blank cover plate at the convenience outlet;
discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until
1
approximately
/
-in (13 mm) under screw heads are
2
exposed. Press the gasket over the screw heads. Slip the
backing plate over the screw heads at the keyhole slots
and align with the gasket; tighten the two screws until
snug (do not over-tighten).
Mount the weatherproof cover to the backing plate as
shown in Fig. 28. Remove two slot fillers in the bottom of
the cover to permit service tool cords to exit the cover.
Check for full closing and latching.
COVER – WHILE-IN-USE
WEATHERPROOF
Fig. 28 - - Weatherproof Cover Installation
23
C09093
Cover:
A
weatherproof
TO
UNIT
AND
RECEPTACLE
NOT SHOWN
BASE PLATE FOR
GFCI RECEPTACLE
C09022