POINT NAME04
Space Temp / Zone Temp
Supply Air Temperature
Outdoor Air Temperature
Space Temperature Offset Pot
Safety Chain Feedback
Compressor Safety Status
Fire Shutdown Status
Enthalpy Status
Humidistat Input Status
Zone Temperature
Indoor Air CO2
Outdoor Air CO2
Space Relative Humidity
Supply Fan Status*
Filter Status*
Door Contact Input*
Occupancy Contact*
Economizer Output
Supply Fan Relay State
Compressor 1 Relay State
Compressor 2 Relay State
Heat Stage 1 Relay State
Heat Stage 2 Relay State
Power Exhaust Relay State
Perfect Humidity Relay State
LEGEND
AI
---
Analog Input
AO ---
Analog Output
DI
---
Discrete Input
DO ---
Discrete Output
*
These inputs (if installed) take the place of the default input on the specific channel according to schematic.
Parallel pins J5 ---1 = J2 ---6, J5 ---3 = J1 ---10, J5 ---5 = J1 ---2 are used for field---installation.
The RTU Open controller requires the use of a Bryant
space sensor. A standard thermostat cannot be used with
the RTU Open system.
Supply Air Temperature (SAT) Sensor —
On FIOP- - equipped 580J units, the unit is supplied with a
supply- - air temperature (SAT) sensor (33ZCSENSAT). This
sensor is a tubular probe type, approx 6- - inches (152 mm) in
length. It is a nominal 10- - k ohm thermistor.
The SAT is factory- - wired. The SAT probe is wire- - tied to the
supply- - air opening in its shipping position. Remove the
sensor for installation. Re- - position the sensor in the flange
of the supply- - air opening or in the supply air duct (as
required by local codes). Drill or punch a
flange or duct. Use two field- - supplied, self- - drilling screws
to secure the sensor probe in a horizontal orientation. See
Fig. 40.
Outdoor Air Temperature (OAT) Sensor —
The OAT is factory- - mounted in the EconoMi$er2 (FIOP or
accessory). It is a nominal 10k ohm thermistor attached to
an eyelet mounting ring.
Table 5 – RTU Open Controller Inputs and Outputs
BACnet OBJECT
NAME
DEDICATED INPUTS
zone_temp
sa_temp
oa_temp
stpt_adj_offset
safety_status
comp_status
firedown_status
enthalpy_status
humstat_status
n/a
CONFIGURABLE INPUTS
iaq
oaq
space_rh
sfan_status
filter_status
door_contact_status
occ_contact_status
OUTPUTS
econ_output
sfan
comp_1
comp_2
heat_1
heat_2
pexh
dehum
1
/
- - in. hole in the
2
TYPE OF I/O
AI (10K Thermistor)
AI (10K Thermistor)
AI (10K Thermistor)
AI (100K Potentiometer)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
n/a
AI (4--- 20 ma)
AI (4--- 20 ma)
AI (4--- 20 ma)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
AO (4--- 20ma)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC, 1A)
SUPPLY AIR
TEMPERATURE
SENSOR
SUPPLY AIR
Fig. 40 - - Mounting Location for Supply Air
Temperature (SAT) Sensor on 580J Units
31
CONNECTION PIN
NUMBER(S)
J20--- 1 & 2
J2--- 1 & 2
J2--- 3 & 4
J20--- 3 & 4
J1--- 9
J1--- 2
J1--- 10
J2--- 6 & 7
J5--- 7 & 8
J13--- 1, 2, 3, 4
J4--- 2 & 3 or J4--- 5 & 6
J5--- 1 or J5--- 3 or J5--- 5
J2--- 5
J1--- 4
J1--- 8
J1--- 7
J1--- 6
J1--- 5
J11--- 1 & 3
J11--- 7, 8
ROOF
CURB
RETURN AIR
C13783