Units Without Factory−Installed Non−Fused Disconnect; All Units; Convenience Outlets - Bryant 581J series Installation Instructions Manual

Hide thumbs Also See for 581J series:
Table of Contents

Advertisement

9. Install the handle on to the painted cover horizontally
with the red arrow pointing to the left.
10. Secure the handle to the painted cover with (2) screws
and lock washers supplied.
11. Engaging the shaft into the handle socket, re−install
(3) hex screws on the NFD enclosure.
12. Re−install the unit front panel.
Fig. 27 − Handle and Shaft Assembly for NFD
Units Without Factory−Installed
Non−Fused Disconnect —
When installing units, provide a disconnect switch per
NEC (National Electrical Code) of adequate size.
Disconnect sizing data is provided on the unit informative
plate. Locate on unit cabinet or within sight of the unit per
national or local codes. Do not cover unit informative
plate if mounting the disconnect on the unit cabinet.
All Units —
All field wiring must comply with NEC and all local
codes. Size wire based on MCA (Minimum Circuit Amps)
on the unit informative plate. See Fig. 24 and unit label
diagram for power wiring connections to the unit and
equipment ground. Maximum wire size is #4 ga AWG
(copper only) per pole on contactors and #2ga AWG
(copper only) per pole on optional non−fused disconnect.
Provide a ground−fault and short−circuit over−current
protection device (fuse or breaker) per NEC Article 440
(or local codes). Refer to unit informative data plate for
MOCP (Maximum Over−current Protection) device size.
All field wiring must comply with the NEC and local
requirements.
All units except 208/230-v units are factory wired for the
voltage shown on the nameplate. If the 208/230-v unit is
to be connected to a 208-v power supply, the control
transformer must be rewired by moving the black wire
1
with the
/
-in. female spade connector from the 230−v
4
connection and moving it to the 208-v
terminal on the primary side of the transformer. Refer to
unit label diagram for additional information.
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate. See
Tables 8 and 9. On 3−phase units, voltages between
phases must be balanced within 2% and the current within
10%. Use the formula shown in the legend for Tables 8
and 9, Note 3 (see page 36) to determine the percent of
voltage imbalance. Operation on improper line voltage or
excessive phase imbalance constitutes abuse and may
cause damage to electrical components. Such operation
would invalidate any applicable Bryant warranty.
NOTE: Check all factory and field electrical connections
for tightness.
Convenience Outlets —
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
C12279
Lock−out and tag−out this switch, if necessary.
Two types of convenience outlets are offered on 581J
models: Non−powered and unit−powered. Both types
provide
circuit−interrupter) duplex receptacle rated at 15−A
behind a hinged waterproof access cover, located on the
end panel of the unit. See Fig. 28.
Installing
while-in-use cover for the factory-installed convenience
outlets is now required by UL standards. This cover
cannot be factory-mounted due its depth; it must be
1
/
-in. male
4
installed
convenience outlet is covered with a blank cover plate.
The weatherproof cover kit is shipped in the unit's control
box. The kit includes the hinged cover, a backing plate
and gasket.
19
WARNING
!
Convenience
Outlet
GFCI
Pwd-CO
Fuse
Switch
Control Box
Access Panel
Fig. 28 − Convenience Outlet Location
a
125−volt
GFCI
Weatherproof
Cover:
at
unit
installation.
Pwd-CO
Transformer
C08128
(ground−fault
A
weatherproof
For
shipment,
the

Advertisement

Table of Contents
loading

Table of Contents