Programming The Controller - Siemens SIMATIC TI505 User Manual

Smart slice discrete i/o module
Hide thumbs Also See for SIMATIC TI505:
Table of Contents

Advertisement

3.1

Programming the Controller

3-2
Programming and Assigning I/O Points
Refer to the program design manual for your controller for specific details
on designing a program.
The Smart Slice appears to the controller as a high-density, 16-point input
and 8-point output module as shown in Table 3-1. Since the Smart Slice has
10 inputs and 6 outputs, the balance of 6 input points and 2 output points
are not used in the I/O configuration table.
Density
Inputs
High
16
Table 3-2 shows how the I/O address is determined for a module with the
starting address of 81.
Program
Corresponding
Input
Module Input
Address
Address
X81
X82
X83
X84
X85
X86
X87
X88
X89
X90
X10
Table 3-1 I/O Configuration
Outputs
I/O Points
8
X1–10
X11–16
Y17–22
Y23–24
Table 3-2 Addressing Example
Program
Output
Address
X1
Y97
X2
Y98
X3
Y99
X4
Y100
X5
Y101
X6
Y102
X7
X8
X9
Values
Input points 1–10
Not used
Output points 1–6
Not used
Corresponding
Module Output
Address
Y17
Y18
Y19
Y20
Y21
Y22