Parameter
Description
r0050
CO / BO: Active command data set
r0051[0...1]
CO: Active inverter data set (DDS)
r0052.0...15
CO / BO: Active status word 1
r0053.0...15
CO / BO: Active status word 2
P0100
Europe / North America
0
1
2
r0206
Rated inverter power [kW] / [hp]
r0207[0...2]
Rated inverter current [A]
r0208
Rated inverter voltage [V]
r0209
Maximum inverter current [A]
P0304[0...2]
Rated motor voltage [V]
P0305[0...2]
Rated motor current [A]
P0307[0...2]
Rated motor power
P0308[0...2]
Rated motor cosφ
P0309[0...2]
Rated motor efficiency [%]
P0310[0...2]
Rated motor frequency [Hz]
P0311[0...2]
Rated motor speed [RPM]
P0335[0...2]
Motor cooling
0
1
2
3
P0340[0...2]
Calculation of motor parameters
0
1
2
P0507
Application macro
r0512
CO: Scaled filtered frequency
P0604[0...2]
Threshold motor temperature [°C]
P0640[0...2]
Motor overload factor [%]
P0700[0...2]
Selection of command source
0
1
P0701[0...2]
Function of digital input 1
0
1
2
3
4
9
10
11
12
13
14
15
P0702[0...2]
Function of digital input 2
P0703[0...2]
Function of digital input 3
P0704[0...2]
Function of digital input 4
P0712 [0...2]
Analog / digital input 1
P0713[0...2]
Analog / digital input 2
P0717
Connection macro
r0722.0...12
CO / BO: Digital input values
18
Europe [kW], motor base frequency is 50 Hz
North America [hp], motor base frequency is 60 Hz
North America [kW], motor base frequency is 60 Hz
Self-cooled: Shaft mounted fan attached motor (IC410 or IC411)
Force-cooled: Separately powered cooling fan (IC416)
Self-cooled and internal fan
Force-cooled and internal fan
No calculation
Complete parameterization
Calculation of equivalent circuit data
Factory default setting
Operator panel (keypad)
Digital input disabled
ON / OFF1
ON reverse / OFF1
OFF2 - coast to standstill
OFF3 - quick ramp-down
Fault acknowledge
JOG right
JOG left
Reverse
MOP up (increase frequency)
MOP down (decrease frequency)
Fixed frequency selector bit0
Range
Factory default
-
-
-
-
-
-
-
-
0 - 2
0
-
-
-
-
-
-
-
-
10 - 2000
400
0.01 - 10000.00
1.86
0.01 - 2000.00
0.75
0.000 - 1.000
0.000
0.0 - 99.9
0.0
12.00 - 599.00
50.00
0 - 40000
1395
0 - 3
0
0 - 4
0
3
Calculation of V/f control data
4
Calculation of controller settings only
0 - 255
0
-
-
0.0 - 200.0
130.0
10.0 - 400.0
150.0
0 - 5
1
2
Terminal
5
USS / MBUS on RS485
0 - 99
0
16
Fixed frequency selector bit1
17
Fixed frequency selector bit2
18
Fixed frequency selector bit3
22
QuickStop Source 1
23
QuickStop Source 2
24
QuickStop Override
25
DC brake enable
27
Enable PID
29
External trip
33
Disable additional freq setpoint
99
Enable BICO parameterization
0 - 99
0
0 - 99
9
0 - 99
15
0 - 99
0
0 - 99
0
0 - 255
0
-
-
Acc. level
2
2
2
2
1
2
2
2
2
1
1
1
1
1
1
1
2
2
1
2
2
2
1
2
2
2
2
2
2
1
2
Getting Started