  SETUP OPERATION
Select operation to edit
  OPERATION          STATE
1=AUTO SEQUENCING      OFF
2=STANDBY TESTING      OFF
3=FAILED STANDBY       N
4=HOLD DELAY           10:00
5=RESTART DELAY        00:06
6=RETURN TO SETUP MENU
7=RETURN TO MAIN MENU
SELECT A NUMBER:2
>STANDBY TESTING- N FOR ON, F FOR OFF
>[N]
>[N]
>COMMAND SUCCESSFUL
>EVERY ## DAYS
>[03] DAYS
>[
>COMMAND SUCCESSFUL
>AT
>[00:00]
>[
>COMMAND SUCCESSFUL
>FOR
>[10] MIN
>[
>COMMAND SUCCESSFUL
Failed Standby
For details on this feature, see
Vertiv | Liebert® AC4 User Manual |
Specify Failed Standby Response
on page 63.