From the Setup System Operation Menu, use the arrows to choose Standby Testing, then
press Enter.
In the Change Standby Testing screen, press Enter to edit
Standby Testing, then use the arrows to choose ON to activate
or OFF to deactivate the standby testing feature. Press Enter.
Select the desired interval for how frequently the testing should
occur in the Every 03 Days field. The default is 3 days; valid
entries range from 0 to 99 days.
For each digit, use the arrows to choose a number from 0 to
9, then press Enter to advance to the next digit.
When finished, press Enter to configure the time of day.
Specify the time of day the test should begin in the At 00:00
field. The format is HH:MM for hours and minutes.
Use the arrows to choose from available entries for hours
(00-23), then press Enter to advance to minutes.
Use the arrows to select minutes (00-59).
When finished, press Enter again.
Specify the duration of the test in minutes—the length of time the standby units will be turned
On—in the For 10 Min field. Use the arrows to choose a number from 0 to 59 minutes. The
default is 10 minutes.
When finished, press Enter.