Surge Map Screen - Table View; Figure 37 - Surge Map Screen - Table View (Software Version C.opt.01.19.307 And Later) - York YK Series Operation Manuals

R-134a cooling only, with optiview control center, for electro-mechanical starter, solid state starter and variable speed drive
Hide thumbs Also See for YK Series:
Table of Contents

Advertisement

FORM 160.54-O1
ISSUE DATE: 9/10/2014
(SOFTWARE VERSION C.OPT.01.19.307 AND LATER)

FIGURE 37 - SURGE MAP SCREEN - TABLE VIEW (SOFTWARE VERSION C.OPT.01.19.307 AND LATER)

OVERVIEW
The surge map can be shown in either Table (default) or
List view as selected with the MAP VIEW key. Shown
above is the Table View.
In this view, a table is used to graphically represent the
surge map in the view window. The X-Axis is Delta
P/P, the Y-Axis is Pre-rotation Vanes position and each
drive frequency point in the surge map is represented
by an "X". To view the details of any mapped point,
position the green box (□) over the desired "X" using
the keypad arrow keys (▲▼◄►). The drive Out-
put Frequency, Pre-rotation Vanes Position and Delta
P/P of the selected point is displayed at the bottom of
the screen under selected. The default position for the
green box is in the upper left corner of the view win-
dow. Once moved, it will remain at the last position.
The Present Operating conditions are indicated with an
"*" (as shown above) and are detailed at the bottom
of the screen under present. If the present condition is
the same as a mapped point, the "*" will be replaced
by an "O".
This screen is applicable to Variable Speed Drives
(VSD) (with the Motor Communications Protocol
Setpoint set to MODBUS; ACC Board is not pres-
JOHNSON CONTROLS

SURGE MAP SCREEN - TABLE VIEW

SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
ent) and Medium Voltage Variable Speed Drives (MV
VSD). It is not accessible if equipped with a VSD in
YORK Motor Communications Protocol Setpoint con-
figuration (ACC Board is present).
Requires a login access level of SERVICE.
Service Technicians refer to the OptiView
Control Center - Service Instructions
(Form 160.54-M1) for operation instruc-
tions and explanation of all programmable
setpoints and displayed values.
DISPLAY ONLY
Mapping Inhibited (LED)
Illuminates while the Microboard ACC function is not
permitted to map points or reduce speed due to unsta-
ble Leaving Chilled Liquid Temperature, manual speed
control, current limit in effect (chiller FLA only) or dur-
ing Soft Shutdown (software version C.OPT.01.21.307
and later). Otherwise, it is extinguished.
ACC Surge Detected (LED)
Illuminates momentarily when a surge is detected by
the ACC function in the Microboard, while the drive is
running at less than maximum frequency.
LD15430