Details Screen - Emerson AMS Trex User Manual

Hide thumbs Also See for AMS Trex:
Table of Contents

Advertisement

Fieldbus Diagnostics application
2.
Related information
5.8

Details screen

By default, the Details screen displays information about the DC voltage, noise, and
fieldbus signal measurements, including:
Note
By default, the Details screen is configured to show all the measurement data in columns, which do
not fit on one screen. Scroll to the right on the screen to view additional columns. (To view only the
measurements and the units, tap Settings > Show Min, Max, Avg to remove the checkmark.)
If a measurement is higher or lower than the set minimum or maximum values in the
measurement criteria, the measurement is highlighted red or orange. Press and hold the
measurement to display a Help option that lists some troubleshooting information. You
can open Help for all cells on the Details screen.
160
The measurement status appears on the screen.
c. If the signal measurement status is "INACTIVE" or if you want to identify the
device tags that are listed on the Details screen, tap Go Online.
If the FOUNDATION fieldbus device is not powered, do the following:
a. Connect the lead set to the FF terminals on the Trex unit and directly to the
communication terminals on the unpowered device. Ensure no other wires are
connected to the device and there is no power to the device. Do not attach to a
junction box.
b. Connect the FOUNDATION fieldbus Power Plug to the FF pwr terminal and the
positive (red) FF terminal on the lead set.
c. Open Fieldbus Diagnostics.
d. On the Fieldbus Diagnostics Overview screen, tap Power supply to enable power to
the device. The Trex unit powers the device.
e. If the signal measurement status is "INACTIVE" or if you want to identify the
device tags that are listed on the Details screen, tap Go Online.
View the live measurement values in Fieldbus Diagnostics
Set the range of values for the GOOD and BAD status
The live measurement values, which are continuously updated.
The units for each measurement.
The minimum, maximum, and average measurement value.
The number of devices on the fieldbus segment.
The addresses of each device detected on the fieldbus segment. The device tag is
also displayed if you selected Go Online on the Fieldbus Diagnostics Overview screen.