3 SPECIFICATIONS
4095
4000
2000
0
–96
–2000
–4000
–4096
–30
Analog input
Number
range setting
1)
4 to 20 mA
2)
0 to 20 mA
User range setting
(2) Current input characteristic
A current input characteristic graph is shown in Figure 3.2.
–20
–10
Offset value
4 mA
0 mA
1
Figure 3.2 Current input characteristic
POINT
(1) Do not input an analog input current of more than ± 30 mA. A breakdown may
result due to overheating.
(2) Set the offset/gain values for the user setting range
the following conditions are satisfied.
{ (Gain value) – (Offset value) } > 5.5 mA
(3) When an analog value that exceeds the range of the digital output value
entered, the digital output value will be fixed at the maximum or minimum
value.
• For 0 to 4000, the range for the digital output value is from –96 to 4095.
Analog input practical range
2)
4
0
Analog input current (mA)
Gain value
Digital output value
20 mA
20 mA
1
3 - 4
1)
10
20
2
0 to 4000
–4000 to 4000
1 within a range in which
MELSEC-Q
30
Maximum
resolution
4
A
5
A
2 is