Mitsubishi Q64AD User Manual page 16

Melsec-q serires analog-digital converter module
Hide thumbs Also See for Q64AD:
Table of Contents

Advertisement

3 SPECIFICATIONS
4095
4000
2000
0
–96
–2000
–4000
–4096
–15
Analog input
Number
range setting
1)
1 to 5 V
2)
0 to 5 V
3)
–10 to 10 V
4)
0 to 10 V
User range setting
(1) Voltage input characteristic
A voltage input characteristic graph is shown in Figure 3.1.
–10
–5
Offset value
1 V
0 V
0 V
0 V
1
Figure 3.1 Voltage input characteristic
POINT
(1) Do not input an analog input voltage of more than ± 15 V. The input elements
may be damaged.
(2) Set the offset/gain values for the user setting range
the following conditions are satisfied.
{ (Gain value) – (Offset value) } > 1.5 V
(3) When an analog value that exceeds the range for the digital output value
entered, the digital output value will be fixed at the maximum or minimum value.
• For 0 to 4000, the range for the digital output value is from –96 to 4095.
• For –4000 to 4000, the range for the digital output value is from –4096 to 4095.
Analog input practical range
2)
1
0
Analog input voltage (V)
Gain value
Digital output value
5 V
5 V
10 V
10 V
1
3 - 3
3) 4)
1)
5
10
2
0 to 4000
–4000 to 4000
0 to 4000
–4000 to 4000
1 within a range in which
MELSEC-Q
15
Maximum
resolution
1.0 mV
1.25 mV
2.5 mV
2.5 mV
2 is

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q68advQ68adi

Table of Contents