Unit Dimensions - 20 Ton - York SUNLINE 2000 Installation Manual

Single package heat pump
Hide thumbs Also See for SUNLINE 2000:
Table of Contents

Advertisement

66396-YIM-C-1004
FIGURE 10 - UNIT DIMENSIONS - 20 TON
TABLE 11: MINIMUM CLEARANCES (MM/IN.)
LOCATION
Front
Back
Left Side (Filter Access)
Right Side (Cond. Coil)
1
Below Unit
2
Above Unit
1.
Units (applicable in U.S.A. only) may be installed on
combustible floors made from wood or class A, B or C
roof covering material.
2.
Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct outdoor air dis-
charge outlet.
NOTE:
Units and ductwork are approved for zero clearance to
combustible materials when equipped with electric heat-
ers.
Unitary Products Group
CLEARANCE
914 mm/36"
610 mm/24" (Less Economizer)
1245 mm/49" (With Economizer
610 mm/24" (Less Economizer)
914 mm/36" (With Economizer)
914 mm/36"
0 mm/0"
1829 mm/72" With 914 mm/36"
Maximum Horizontal Overhang
For Condenser Air Discharge)
All dimensions are in millimeters and
inches. They are subject to change with-
out notice. Certified dimensions will be
provided upon request.
TABLE 12: UTILITIES ENTRY DATA (MM/IN.)
HOLE
OPENING SIZE (DIA.)
28.6 mm/1-1/8" KO
A
19.1 mm/3/4" NPS (Fem.)
92.1 mm/3-5/8" KO
B
76.2 mm/3" NPS (Fem.)
NOTE:
All entry holes should be field sealed to prevent rain
water entry into building.
USED FOR
Front
Control Wiring
Bottom
Front
Power Wiring
Bottom
19