Clearances; Unit Center Of Gravity; Unit Dimensions; Unit Height - York Predator BP078 Installation Manual

Single package heat pump high efficiency
Table of Contents

Advertisement

X
LEFT
Unit Model Number
BP078
BP090
BP102
BP120
BP150
FIGURE 7 -

UNIT CENTER OF GRAVITY

FIGURE 8 -

UNIT DIMENSIONS

TABLE 6: UNIT HEIGHT
Unit Model Number
BP078
BP090
BP102
BP120
BP150
10
Y
FRONT
X
Y
47 1/2
25 1/2
38
23
47 1/2
25 1/2
47 1/2
25 1/2
47 1/2
25 1/2
X
50 3/4
42
50 3/4
50 3/4
50 3/4

CLEARANCES

All units require particular clearances for proper operation
and service. Refer to Table 7 for clearances required for con-
struction, servicing, and proper unit operation.
Do not permit overhanging structures or shrubs to
obstruct condenser air discharge outlet, combustion
air inlet or vent outlets.
TABLE 7: UNIT CLEARANCES
*
72"
Top
Front
36"
36"
Rear
*.
Units must be installed outdoors. Overhanging struc-
ture or shrubs should not obstruct condenser air dis-
charge outlet.
†.
To remove the slide-out drain pan, a rear clearance of
sixty inches is required. If space is unavailable, the
drain pan can be removed through the front by separat-
ing the corner wall.
‡.
Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.
127421-YIM-C-0606
Right
12"
Left
36"
0"
Bottom
Unitary Products Group

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents