Installation; Installation Safety Information; Limitations; Location - York SUNLINE 2000 Installation Manual

Single package heat pump
Hide thumbs Also See for SUNLINE 2000:
Table of Contents

Advertisement

66396-YIM-C-1004

INSTALLATION

INSTALLATION SAFETY INFORMATION:

Read these instructions before continuing this appli-
ance installation. This is an outdoor combination heat-
ing and cooling unit. The installer must assure that
these instructions are made available to the consumer
and with instructions to retain them for future reference.
1. Install this furnace only in a location and position
as specified on Page 7 of these instructions.
2. This equipment is not to be used for temporary
heating of buildings or structures under construc-
tion.

LIMITATIONS

These units must be installed in accordance with the
following national and local safety codes:
In U.S.A.:
National Electrical Code ANSI/NFPA No. 70.
TABLE 1: UNIT APPLICATION DATA
UNIT MODEL NUMBER
Voltage Variation,
Min. / Max.
3
Supply Air m
/s (CFM), Min. / Max.
Wet Bulb Temperature of Air on
Evaporator Coil, Min. / Max.
Dry Bulb Temperature of Air on
Condenser Coil, Min. / Max.
1.
Utilization range "A" in accordance with ARI Standard 110.

LOCATION

Use the following guidelines to select a suitable loca-
tion for these units.
1. Unit is designed for outdoor installation only.
2. Condenser coils must have an unlimited supply of
air.
3. Where a choice of location is possible, position the
unit on either north or east side of building.
4. For ground level installation, use a level concrete
slab with a minimum thickness of 102 mm (4"). The
length and width should be at least 152 mm (6")
Unitary Products Group
380/415-3-50
1
°C
°F
°C
°F
Local gas utility requirements.
In Canada:
Current Canadian Electrical Code C22.1.
Local plumbing and waste water codes.
Other applicable local codes.
Refer to the Unit Application Data table and to the Elec-
tric Heat Application Data table.
If components are to be added to a unit to meet local
codes, they are to be installed at the dealer's and/or
the customer's expense.
Size of unit for proposed installation should be based
on heat loss/heat gain calculation made according to
the methods of the Air Conditioning Contractors of
America (ACCA).
This furnace is not to be used for temporary heating of
buildings or structures under construction.
342/456
2.9 (6,000) / 4.7 (9,400)
-18 / 49
greater than the unit base rails. Do not tie slab to
the building foundation.
5. Roof structures must be able to support the weight
of the unit and its options and/or accessories. Unit
must be installed on a solid level roof curb or
appropriate angle iron frame.
6. Maintain level tolerance to 13 mm (1/2") maximum
across the entire length or width of the unit.
If a unit is to be installed on a roof curb or special frame
®
other than a
roof curb, gasketing must be applied
York
to all surfaces that come in contact with the unit under-
side.
BQ240
14 / 22
57 / 72
0 / 120
7