Technical specifications
6.1 Technical specifications
Article number
Cable length
shielded, max.
•
unshielded, max.
•
Encoder
Connectable encoders
2-wire sensor
•
Isochronous mode
Isochronous operation (application synchro-
nized up to terminal)
Interrupts/diagnostics/status information
Alarms
Diagnostic alarm
•
Hardware interrupt
•
Diagnostic messages
Monitoring the supply voltage
•
Wire-break
•
Short-circuit
•
Diagnostics indication LED
Monitoring of the supply voltage (PWR-
•
LED)
Channel status display
•
for channel diagnostics
•
for module diagnostics
•
Potential separation
Potential separation channels
between the channels
•
between the channels and backplane bus
•
between the channels and the power sup-
•
ply of the electronics
Isolation
Isolation tested with
Altitude during operation based on sea level
Ambient air temperature-barometric pres-
•
sure-altitude
24
6ES7131-6FD01-0BB1
1 000 m
600 m
Yes
No
No
No
No
No
No
Yes; green PWR LED
Yes; Green LED
No
Yes; green/red DIAG LED
No
Yes
No
2 545 V DC/2 s (routine test)
On request: Ambient temperatures lower than 0
°C (without condensation) and/or installation
altitudes greater than 2 000 m
Digital input module DI 4x120..230VAC ST (6ES7131-6FD01-0BB1)
Manual, 09/2017, A5E32043398-AC