Article number
Encoder supply
Number of outputs
Short-circuit protection
Output current
up to 60 °C, max.
•
Power loss
Power loss, typ.
Address area
Address space per module
Inputs
•
Hardware configuration
Automatic encoding
Mechanical coding element
•
Selection of BaseUnit for connection variants
1-wire connection
•
2-wire connection
•
3-wire connection
•
4-wire connection
•
Digital inputs
Number of digital inputs
Input characteristic curve in accordance with
IEC 61131, type 3
Input voltage
Type of input voltage
•
Rated value (AC)
•
for signal "0"
•
for signal "1"
•
Input current
for signal "1", typ.
•
Input delay (for rated value of input voltage)
for standard inputs
–
parameterizable
–
at "0" to "1", min.
–
at "0" to "1", max.
–
at "1" to "0", min.
–
at "1" to "0", max.
Digital input module DI 4x120..230VAC ST (6ES7131-6FD01-0BB1)
Manual, 09/2017, A5E32043398-AC
6ES7131-6FD01-0BB1
4
No; when using BU type B1, a fuse with 10 A
tripping current must be provided
10 A
1 W; Active power, load voltage 230 V, all inputs
connected with 230 V, 50 Hz
1 byte; + 1 byte for QI information
Yes
Yes
BU type B1
BU type B1
BU type B1
BU type B1 + potential distributor module
4
Yes
120/230V AC (47 Hz to 63 Hz)
230 V
0V AC to 40V AC
74 V AC to 264 V AC
10.8 mA
No
1.5 ms
4 ms
10 ms
10 ms
Technical specifications
6.1 Technical specifications
23