Appendix
A.1
List of important alarms and faults
Axxxxx: Alarm
Fyyyyy: Fault
Table A- 1
The most important alarms and faults
Number Cause
F07085 Control parameters were compulsorily changed for the
following reasons:
They exceeded dynamic limits due to different
•
parameters.
They are not applicable because of properties of
•
the detected hardware that are not present.
–
Fault value (r0949, interpret as decimal):
Changed parameter number.
–
340: The automatic calculation of the motor and
control parameters was performed (p0340 = 1),
because the vector control was later activated
as a configuration (r0108.2).
F07802 Infeed or drive does not reply a 'ready' after an internal
actuation command.
Monitoring time too short.
•
DC link voltage not available.
•
Associated infeed or drive of the reporting
•
components defective.
Supply voltage incorrectly set.
•
Getting Started
Getting Started, (GS1) 04/2014, 6SL3097-4AG00-0BP3
Remedy
Not necessary.
No parameter change is necessary as the parameters
have already been limited to a reasonable level.
Extend monitoring time (p0857).
•
Ensure the DC link voltage. Check the DC link
•
voltage. Enable the infeed.
Replace associated infeed or drive of the reporting
•
components.
Check settings of the supply voltage (p0210).
•