Parameters accessible with Function Code 03, 06,10h
Scheduler
Procedure for Uploading Setpoint Schedules

Table 6-14 Steps to Upload a Setpoint Schedule using Modbus Function Codes 3, 6, 16

Step
1
Set the scheduler to RESET by writing any number to Reset (p. 70). This can be done either
with function code 6 or 16.
2
Load the schedule into the setpoint scheduler block by writing the schedule number to
Current Program Number (p. 69). This is a floating point register and requires a multiple
register write (function code 16)
3
Read the header information desired. Guaranteed Soak Limits 1-8 (p. 69), Jog Segment (p.
69), Time Units (p. 70). Use function code 3.
4
Read the information for each segment in the schedule (p. 71) using function code 3.
Scheduler parameters
This table contains Values of Schedulers. Fixed addresses are for Scheduler #1; see Table 6-1 for fixed
addresses of other Schedulers.
Parameters commonly used for controlling a scheduler are marked with a single asterisk*.
Parameters commonly used to define a schedule are marked with two asterisks **.
The addresses given in Table 6-15 do not necessarily apply to schedulers in the custom map. For custom
addresses view or print a report in HC Designer.
Fixed
Fixed
Address
Register
(hex)
(decimal)
3000
12289
3002
12291
3004
12293
3006
12295
3008
12297
300A
12299
300C
12301
300E
12303
3010
12305
3012
12307
3014
12309
3016
12311
3018
12313
301A
12315
301C
12317
301E
12319
68

Table 6-15 Scheduler Parameters

Parameter
Scheduler Output 1**
Scheduler Output 2**
Scheduler Output 3**
Scheduler Output 4**
Scheduler Output 5**
Scheduler Output 6**
Scheduler Output 7**
Scheduler Output 8**
Scheduler Auxiliary Output 1**
Scheduler Auxiliary Output 2**
Scheduler Auxiliary Output 3**
Scheduler Auxiliary Output 4**
Scheduler Auxiliary Output 5**
Scheduler Auxiliary Output 6**
Scheduler Auxiliary Output 7**
Scheduler Auxiliary Output 8**
HC900 Process Controller Communications User Guide
Action
Access Notes
R
Floating Point in Engineering Units.
R
Floating Point in Engineering Units.
R
Floating Point in Engineering Units.
R
Floating Point in Engineering Units.
R
Floating Point in Engineering Units.
R
Floating Point in Engineering Units.
R
Floating Point in Engineering Units.
R
Floating Point in Engineering Units.
R
Floating Point in Engineering Units.
R
Floating Point in Engineering Units.
R
Floating Point in Engineering Units.
R
Floating Point in Engineering Units.
R
Floating Point in Engineering Units.
R
Floating Point in Engineering Units.
R
Floating Point in Engineering Units.
R
Floating Point in Engineering Units.
Revision 13