Parameters accessible with Function Code 03, 06,10h
Alternator
Fixed
Fixed
Address
Register
(hex)
(decimal)
6704
26373
6705
26374
86
Parameter Name
Access Notes
Output Status #1-4
R
Output Status #5-8
R
HC900 Process Controller Communications User Guide
Bit Packed:
Bit 0: Output #1 Enable: 0=NO, 1=YES
Bit 1: Output #1 Used: 0=NO, 1=YES
Bit 2: Output #1 ON: 0=OFF, 1=ON
Bit 3: Unused
Bit 4: Output #2 Enable: 0=NO, 1=YES
Bit 5: Output #2 Used: 0=NO, 1=YES
Bit 6: Output #2 ON: 0=OFF, 1=ON
Bit 7: Unused
Bit 8: Output #3 Enable: 0=NO, 1=YES
Bit 9: Output #3 Used: 0=NO, 1=YES
Bit 10: Output #3 ON: 0=OFF, 1=ON
Bit 11: Unused
Bit 12: Output #4 Enable: 0=NO, 1=YES
Bit 13: Output #4 Used: 0=NO, 1=YES
Bit 14: Output #4 ON: 0=OFF, 1=ON
Bit 15: Unused
Bit Packed:
Bit 0: Output #5 Enable: 0=NO, 1=YES
Bit 1: Output #5 Used: 0=NO, 1=YES
Bit 2: Output #5 ON: 0=OFF, 1=ON
Bit 3: Unused
Bit 4: Output #6 Enable: 0=NO, 1=YES
Bit 5: Output #6 Used: 0=NO, 1=YES
Bit 6: Output #6 ON: 0=OFF, 1=ON
Bit 7: Unused
Bit 8: Output #7 Enable: 0=NO, 1=YES
Bit 9: Output #7 Used: 0=NO, 1=YES
Bit 10: Output # ON: 0=OFF, 1=ON
Bit 11: Unused
Bit 12: Output #8 Enable: 0=NO, 1=YES
Bit 13: Output #8 Used: 0=NO, 1=YES
Bit 14: Output # ON: 0=OFF, 1=ON
Bit 15: Unused