Honeywell HC900 User Manual page 95

Process controller
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

Fixed
Fixed
Address
Register
(hex)
(decimal)
6706
26375
6707
26376
6708
26377
6709
26378
670A
26379
670B
26380
670C
26381
Revision 13
April 2017
Parameter Name
Access Notes
Output Status #9-12
R
Output Status #13-16 R
Request Style
R
Direct Request
W
Rotary Request
W
First on/First off
W
Request
Fixed Request
W
HC900 Process Controller Communications User Guide
Parameters accessible with Function Code 03, 06,10h
Bit Packed:
Bit 0: Output #9 Enable: 0=NO, 1=YES
Bit 1: Output #9 Used: 0=NO, 1=YES
Bit 2: Output #9 ON: 0=OFF, 1=ON
Bit 3: Unused
Bit 4: Output #10 Enable: 0=NO, 1=YES
Bit 5: Output #10 Used: 0=NO, 1=YES
Bit 6: Output #10 ON: 0=OFF, 1=ON
Bit 7: Unused
Bit 8: Output #11 Enable: 0=NO, 1=YES
Bit 9: Output # Used: 0=NO, 1=YES
Bit 10: Output #11 ON: 0=OFF, 1=ON
Bit 11: Unused
Bit 12: Output #12 Enable: 0=NO, 1=YES
Bit 13: Output #12 Used: 0=NO, 1=YES
Bit 14: Output #12 ON: 0=OFF, 1=ON
Bit 15: Unused
Bit Packed:
Bit 0: Output #13 Enable: 0=NO, 1=YES
Bit 1: Output #13 Used: 0=NO, 1=YES
Bit 2: Output #13 ON: 0=OFF, 1=ON
Bit 3: Unused
Bit 4: Output # Enable: 0=NO, 1=YES
Bit 5: Output #14 Used: 0=NO, 1=YES
Bit 6: Output #14 ON: 0=OFF, 1=ON
Bit 7: Unused
Bit 8: Output #15 Enable: 0=NO, 1=YES
Bit 9: Output #15 Used: 0=NO, 1=YES
Bit 10: Output #15 ON: 0=OFF, 1=ON
Bit 11: Unused
Bit 12: Output #16 Enable: 0=NO, 1=YES
Bit 13: Output #16 Used: 0=NO, 1=YES
Bit 14: Output #16 ON: 0=OFF, 1=ON
Bit 15: Unused
Bit Packed:
Bit 0: Direct: 0=NO, 1=YES
Bit 1: Rotary: 0=NO, 1=YES
Bit 2: FOFO: 0=NO, 1=YES
Bit 3: Fixed: 0=NO, 1=YES
Bit 4-15: Unused
Unsigned 16 Integer
Data Ignored
Unsigned 16 Integer
Data Ignored
Unsigned 16 Integer
Data Ignored
Unsigned 16 Integer
Data Ignored
Alternator