Parameters accessible with Function Code 03, 06,10h
Loop Values
Fixed
Fixed
Parameter Name
Address
Register
(hex)
(decimal)
0064
0101
Reset #2
0066
0103
Rate #2
0068
0105
Cycle Time for Analog
Scan
006A
0107
LSP #1
006C
0109
LSP #2
006E
0111
Alarm #2 SP #1
0070
0113
Alarm #2 SP #2
0074
0117
SP Low Limit
0076
0119
SP High Limit
0078
0121
Working Set Point
007A
0123
Output Low Limit
007C
0125
Output High Limit
007E
0127
Output Working Value   
0086
0135
Ratio
0088
0137
Bias
008A
0139
Deviation
008E
0143
Manual Reset
0090
0145
Feed-forward Gain
0092
0147
Local Percent Carbon
Monoxide
0094
0149
Furnace Factor
0096
0151
Percent Hydrogen
0098
0153
On/Off Output
Hysterisis
009A
0155
Carbon Potential
Dewpoint
009C
0157
Three Position Step
Motor Time
00F7
0248
Enable/Disable Fuzzy 
00F8
0249
Demand Tune
Request
00F9
0250
Anti-soot set point limit
enable
00FA
0251
Auto/Manual State
50
Loop type
PID On/
Carb 3Pos AMB
Off
  
  
  
  
  
  
  
  
  
  
HC900 Process Controller Communications User Guide
Access Notes
R/W
Floating Point in Repeats/Minute or
Minutes/Repeat as configured in the HC900.
R/W
Floating Point in Minutes
R
Floating Point in Seconds
R/W
Floating Point in Engineering Units
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units. Operator Limit
R/W
Floating Point in Engineering Units. Operator Limit
R/W
Floating Point in Engineering Units.
On a write to this register the instrument will update
the proper set point according to the loop's
currently selected set point.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units. Auto/Man bias
block, value is Read-Only
R
Floating Point in Engineering Units.
(SP-PV)
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in percent of input span
R/W
Floating Point in Engineering Units
R/W
Floating Point in seconds
R/W
Bit Packed
Bit 0: 0:Disable; 1:Enable
R/W
Bit Packed (one shot action, activates autotuning
until autotuning completed)
Bit 0: 0:Off; 1:On
Bit 1-15: Unused
R/W
Bit Packed
Bit 0: 0:Off; 1:On
Bit 1-15: Unused
R/W
Bit Packed
Bit 0: 0:Manual; 1:Auto
Bit 1-15: Unused
Revision 13