Parameters accessible with Function Code 03, 06,10h
Loop Values
Fixed
Fixed
Parameter Name
Address
Register
(hex)
(decimal)
0064
0101
Reset #2
0066
0103
Rate #2
0068
0105
Cycle Time for Analog
Scan
006A
0107
LSP #1
006C
0109
LSP #2
006E
0111
Alarm #2 SP #1
0070
0113
Alarm #2 SP #2
0074
0117
SP Low Limit
0076
0119
SP High Limit
0078
0121
Working Set Point
007A
0123
Output Low Limit
007C
0125
Output High Limit
007E
0127
Output Working Value
0086
0135
Ratio
0088
0137
Bias
008A
0139
Deviation
008E
0143
Manual Reset
0090
0145
Feed-forward Gain
0092
0147
Local Percent Carbon
Monoxide
0094
0149
Furnace Factor
0096
0151
Percent Hydrogen
0098
0153
On/Off Output
Hysterisis
009A
0155
Carbon Potential
Dewpoint
009C
0157
Three Position Step
Motor Time
00F7
0248
Enable/Disable Fuzzy
00F8
0249
Demand Tune
Request
00F9
0250
Anti-soot set point limit
enable
00FA
0251
Auto/Manual State
50
Loop type
PID On/
Carb 3Pos AMB
Off
HC900 Process Controller Communications User Guide
Access Notes
R/W
Floating Point in Repeats/Minute or
Minutes/Repeat as configured in the HC900.
R/W
Floating Point in Minutes
R
Floating Point in Seconds
R/W
Floating Point in Engineering Units
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units. Operator Limit
R/W
Floating Point in Engineering Units. Operator Limit
R/W
Floating Point in Engineering Units.
On a write to this register the instrument will update
the proper set point according to the loop's
currently selected set point.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units. Auto/Man bias
block, value is Read-Only
R
Floating Point in Engineering Units.
(SP-PV)
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in Engineering Units.
R/W
Floating Point in percent of input span
R/W
Floating Point in Engineering Units
R/W
Floating Point in seconds
R/W
Bit Packed
Bit 0: 0:Disable; 1:Enable
R/W
Bit Packed (one shot action, activates autotuning
until autotuning completed)
Bit 0: 0:Off; 1:On
Bit 1-15: Unused
R/W
Bit Packed
Bit 0: 0:Off; 1:On
Bit 1-15: Unused
R/W
Bit Packed
Bit 0: 0:Manual; 1:Auto
Bit 1-15: Unused
Revision 13
April 2017